EasyManua.ls Logo

Bender ISOMETER isoEV425 - Page 59

Bender ISOMETER isoEV425
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
59
isoEV425_D00126_09_M_XXEN/03.2019
IT system being monitored
Nominal system voltage U
n
with AGH420 .................................................... 3(N)AC, AC 0…690 V/DC 0…1,000 V
Tolerance of U
n
...........................................................................................................................AC +15 %, DC +10 %
Nominal system voltage range U
n
with AGH420 (UL508) ................................................................AC/DC 0…600 V
Frequency range of U
n
..........................................................................................................................DC, 15…460 Hz
Measuring circuit
Permissible system leakage capacitance C
e
(isoEV425)...................................................................................... ≤ 5 F
Permissible system leakage capacitance C
e
(isoEV425HC).............................................................................. ≤ 20 F
Permissible extraneous DC voltage U
fg
......................................................................................................... ≤ 1,150 V
Response values
Response value R
an1
(isoEV425) ................................................................................................ 2…500 kΩ (500 kΩ)*
Response value R
an1
(isoEV425HC)............................................................................................ 2…500 kΩ (200 kΩ)*
Response value R
an2
(isoEV425) ................................................................................................ 1…490 kΩ (100 kΩ)*
Operating uncertainty R
an
(C
e
≤ 5 F)...................................................................................... ±15 %, at least ±1 k
Operating uncertainty R
an
(C
e
> 5 F und R
F
>100 kΩ)............................................... ±(5 % * R
an
/100 kΩ +10 %)
Hysteresis R
an
.................................................................................................................................. 25 %, at least 1 kΩ
Undervoltage detection ................................................................................................................. 30…1.14 kV (off)*
Overvoltage detection .....................................................................................................................31…1.15 kV (off)*
Relative uncertainty U.................................................................................................................... ±5 %, at least ±5 V
Relative uncertainty depending on the frequency
200 Hz...................................................................... -0.03 %/Hz
Hysteresis U .......................................................................................................................................... 5 %, at least 5 V
Time response
Response time t
an
at R
F
= 0.5 x R
an
and C
e
=1 F acc. to IEC 61557-8 ............................................................. ≤ 10 s
Start-up delay t ...................................................................................................................................... 0…10 s (0 s)*
Response delay t
on
................................................................................................................................. 0…99 s (0 s)*
Delay on release t
off
............................................................................................................................... 0…99 s (0 s)*
Displays, memory
Display..................................................................................................... LC display, multi-functional, not illuminated
Display range measured value insulation resistance (R
F
) ........................................................................ 1 kΩ…1 MΩ
Operating uncertainty
(C
e
≤ 5 F)............................................................................................ ±15 %, at least ±1 kΩ
Operating uncertainty
(C
e
> 5 F und R
F
>100 kΩ) ...................................................... ±(5 % * R
F
/100 kΩ +10 %)

Table of Contents

Related product manuals