Operation of the device
36
isoEV425_D00126_09_M_XXEN/03.2019
5.5 Menu "t"
5.5.1 Time configuration
FAC = Factory setting; Cs = User settings
5.6 Menu "SEt"
5.6.1 Function configuration
FAC = Factory setting; Cs = User settings
*applies to isoEV425-D49-4
Display Setting value Description
Value range FAC Cs
t 0 … 10 0 s Start-up delay when starting the
device
ton 0 … 99 0 s Response delay K1 and K2
toff 0 … 99 0 s Delay on release K1 and K2
test
OFF/1 / 24
24 h Repetition time device test
Display Activation Setting value Description
FAC Cs
Value
range
FAC
Cs
off 0 . . . 999
0
Password for
parameter setting
nEt
on/
off*
Test of the system connec-
tion during device test
S.Ct
on
Device test during device
start
FAC Restore factory settings
SYS For Bender Service only