EasyManua.ls Logo

Bender RCMB300 Series - Page 54

Bender RCMB300 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
54
RCMB300-series_D00372_01_M_XXEN/06.2019
Measuring circuit
Internal diameter measuring current transformer ..............................see dimension diagrams Page 18
Characteristics according to IEC 62020 and IEC/TR 60755 ................................. AC/DC sensitive, type B
Measuring range ...................................................................................................................5 mA…20 A
Response value I
Δn
........................................................... 30 mA…3 A (freely configurable), (30 mA)*
Prewarning ...................................................................50 %…100 % I
Δn
(freely configurable), (60 %)
Rated current I
n
CTBC20 when I
Δn
= 30 mA...........................................................................................................40 A
CTBC20 when I
Δn
= 300 mA ........................................................................................................63 A
CTBC20P.........................................................................................................................................80 A
CTBC35 when I
Δn
= 30 mA...........................................................................................................80 A
CTBC35 when I
Δn
= 300 mA ......................................................................................................125 A
CTBC35P.......................................................................................................................................160 A
CTBC60 when I
Δn
= 30 mA.........................................................................................................160 A
CTBC60 when I
Δn
= 300 mA ......................................................................................................250 A
CTBC60P.......................................................................................................................................320 A
CTBC120 when I
Δn
= 100 mA ....................................................................................................330 A
CTBC120P when I
Δn
= 100 mA..................................................................................................630 A
CTBC210 when I
Δn
= 300 mA ....................................................................................................630 A
CTBC210P when I
Δn
= 100 mA..................................................................................................630 A
CTBC210P when I
Δn
= 300 mA............................................................................................... 1000 A
Operating uncertainty .................................................................................................................±17.5 %
Relative uncertainty .................................................................................................................0…–35 %
Test winding.......................................................................................................................................... yes
Possible response values (to be set on the evaluator)
CTBC20, CTBC20P.................................................................................................................10…500 mA
CTBC35, CTBC35P, CTUBC60, CTBC60P ..............................................................................30 mA…10 A
CTBC120P, CTBC210P........................................................................................................100 mA…10 A
CTBC120, CTBC210............................................................................................................300 mA…10 A
Time response
Response delay t
on
............................................................ 50 ms…60 min (freely configurable), (0 s)*
Start-up delay t
an
....................................................................0 s…60 min (freely configurable), (0 s)*
Delay on release t
off
................................................................0 s…60 min (freely configurable), (1 s)*

Table of Contents

Related product manuals