55
RCMB300-series_D00372_01_M_XXEN/06.2019
Operating time t
ae
at 1 x I
Δn
............................................................................................................................. ≤ 230 ms
at 2 x I
Δn
............................................................................................................................. ≤ 180 ms
at 5 x I
Δn
................................................................................................................................ ≤ 70 ms
Response time t
an
= t
ae
+ t
on
Recovery time t
b
.................................................................................................................................≤ 1 s
Indication
Multicolour LED .........................................Refer to "System states: LED and output relays" on page 49.
Inputs
.......................................................................................................................................................T/R, GND
Outputs
Number of changeover contacts ............................................................................................................. 2
Operating principle......................................... N/C* or N/O principle freely configurable (N/C principle)
Switching outputs (K1, K2) .......................................................................................................250 V, 5 A
Switching capacity............................................................................................................ 1500 VA/144 W
Contact data acc. to IEC 60947-5-1
Rated operational voltage AC .........................................................................................250 V/250 V
Utilisation category ....................................................................................................... AC-13/AC-14
Rated operational current AC ................................................................................................. 5 A/3 A
Rated operational voltage DC........................................................................................220/110/24 V
Utilisation category...................................................................................................................... DC12
Rated operational current DC ............................................................................................0.1/0.2/1 A
Minimum current..............................................................................................................10 mA at DC 5 V
Electrical endurance, number of cycles........................................................................................... 10,000
Environment/EMC
EMC ............................................................................................................................................ IEC 62020
Operating temperature........................................................................................................... -25…70 °C
Classification of climatic conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) .............................3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2) ..................................2K11 (except condensation and formation of ice)
Long-term storage (IEC 60721-3-1) ...................1K22 (except condensation and formation of ice)
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ................................................................................................... 3M4
Transport (IEC 60721-3-2).......................................................................................................... 2M4
Long-term storage (IEC 60721-3-1) ........................................................................................ 1M12