S2000M MAINTENANCE GUIDE
9
Note - Alarm indication at LED indicator and sound annunciator is made only if option
‘ALARM SOUND’ is on. Default option setting is ‘on’.
1.2.22 Console allow user to control by relay outputs of signal-start ‘S2000-SP1’ blocks,
and also by ‘Signal-20P’, ‘S2000-4’, ‘Signal-20’ series 02 device outputs. Total number of
controlled outputs is up to 255. Outputs are controlled by given control programs according to
the states of the connected partitions. Relay output can be connected with any number of
partitions (up to 255), and partition can be connected with arbitrary number of the outputs (up to
255). Console support 35 different relay control programs. Control program determines state of
output at different states of connected with it partitions. Relay control program description is
shown in the table 3. Description of partition states are shown in the appendix C. Partitions,
partition links with outputs and control programs are setup at customizing (see. item. 2.1.7.4).
Table 7 Relay executive programs
Number Program name Program description
1 ‘On’ If ‘Intrusion alarm’ or ‘Fire alarm’ - ON;
else OFF output.
2 ‘Off’ If ‘Intrusion alarm’ or ‘Fire alarm’ - OFF;
else ON output.
3 ‘On for a time’ If ‘Intrusion alarm’ or ‘Fire alarm’ - ON for a time;
else OFF output.
4 ‘Off for a time’ If ‘Intrusion alarm’ or ‘Fire alarm’ - OFF for a time;
else ON output.
5 ‘Blinking. Normal state
OFF’
If ‘Intrusion alarm’ or ‘Fire alarm’ - blink (0,5 s ON, 0,5 s
OFF);
else OFF output.
6 ‘Blinking. Normal state
ON’
If ‘Intrusion alarm’ or ‘Fire alarm’ - blink (0,5 s ON, 0,5 s
OFF);
else ON output.
7 ‘Blinking for a time.
Normal state OFF’
If ‘Intrusion alarm’ or ‘Fire alarm’ - blink (0,5 s ON, 0,5 s
OFF) during given time;
else OFF output.
8 ‘Blinking for a time.
Normal state ON’
If ‘Intrusion alarm’ or ‘Fire alarm’ - blink (0,5 s ON, 0,5 с
OFF) during given time;
else ON output
9 ‘LAMP’ If ‘Fire alarm’, ‘Fire prealarm’, ‘Intrusion alarm’, ‘Entry
alarm’ or ‘Arm failed’, then blink (0,5 s ON, 0,5 s OFF);
if ‘Disconnected alarm loop’, “Relay disconnected”, “Fire
trouble”, “Loop open circuit”, “Configuration error”,
“Open relay output ”, “Relay output short circuit”, “Battery
failed”, “AC power failed”, “Power failed”, “2-wire line
short circuit” or “2-wire line trouble”, then blink (0,25 s
ON, 1,75 s OFF);
if there is at least one armed zone, then ON output;
if all zones are disarmed, then OFF output.
10 ‘Alarm output 1’ If all partitions are armed, then ON (close) outputs;
else OFF (open) output.
11 ‘ASPT’ ON for a given time, if at least two zones in partition have
‘Fire alarm’ status and there are no zones having states
"Auxiliary alarm", "Relay disconnected", "Open relay
output", "Relay output short circuit". When the failure
removed the relay output will be ON