D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
.
Bosch Security Systems, Inc. | 11/05 | F01U011024B 49
A B C E F A G H J
Move the transmitter to within
10 ft of the FA400 Receiver, then
retest the wireless transmitter.
• If the values still do not match
the conditions of the wireless
transmitter, remove the
battery from the old
transmitter, and install a new
transmitter.
• If the values now match the
conditions of the wireless
transmitter, then either
relocate the transmitter,
relocate the receiver, or add
an FA570 Repeater to the
system.
After reconfiguring a wireless
system, always retest the
system to ensure all devices
operate correctly.
There is noise on the zonex data wiring.
Refer to TTP48 Noise on Wire on
page
102.
Reprogram the transmitter as a new
transmitter.
Do not reconfigure the transmitter as an
existing transmitter.
You might need to perform this procedure
on more than one transmitter.
On the D8125INV:
1. Enter the passcode, then press [ENT].
2. Press [DIAG].
3. Press [1].
4. Enter the number of a wireless point that is in
trouble, then press [ENT].
5. Refer to Items 1 and 2 in
Figure 27 on page 52,
and refer to Table 27 on page 52.
Does the D8125INV indicate “This RF Point is not
programmed”?
Move the transmitter to within 10 ft. of the
FA400 Receiver, then retest the wireless
transmitter. Refer to Item 2 in
Figure 27 on
page 52, and refer to Table 27 on page 52.
Do the values match the condition of the
wireless transmitter?
A G H J
Replace the battery in the wireless
transmitter, then retest the transmitter.
Do the values match the condition of
the wireless transmitter?
Reprogram the wireless
transmitter, then retest the
transmitter.
• If the values now match
the condition of the
transmitter, then the
problem is corrected.
• If the values still do not
match the condition of the
transmitter, remove the
battery from the
transmitter and replace
the transmitter.
Problem is corrected.
Either relocate the transmitter, relocate the
receiver, or add an FA570 Repeater to the
system.
After reconfiguring a wireless system,
always retest the system to ensure all
devices operate correctly.
Reprogram the transmitter as a new transmitter.
Do not reconfigure the transmitter as an existing
transmitter.
You might need to perform this procedure on
more than one transmitter.
On the D8125INV:
1. Enter the passcode, then press [ENT].
2. Press [DIAG].
3. Press [1].
4. Enter the number of a wireless point that is in trouble,
then press [ENT].
5. Refer to Item 1 and Item 2 in
Figure 27 on page 52,
and refer to Table 27 on page 52.
Does the D8125INV indicate “This RF Point is not
programmed”?
Does item 2 in
Figure 27 indicate “Bad” or
“Missing”?
Figure 28
Refer to
on page 54.
Is the control panel wired to the D8125INV
correctly?
K L M N