DS7200V2-UK Installer's Guide Copyright 2007 Bosch Security Systems, Inc. P/N: 4998152533-02 Page 113
PART IV: CONTROL PANEL PROGRAMMING
Format for Destination 1 (2)
Address:
Format for Destination 1: 0064
Format for Destination 2: 0130
Default: 2 (Contact ID)
Selections:
2 = Contact ID
3 = SIA 300
4 = Basic Pager
6 = BSIA Fast Format
7 = Personal Dialing Format
11 = SIA 300 with Text Blocks
If you enable network communication, the control panel automatically selects Contact ID as the reporting format. Contact ID
only supports four-digit account numbers. As a result, the control panel automatically truncates account numbers to four digits.
Alternate Communication Options
Address Range:
IP Address 1, Destination 1: 3506
IP Address 2, Destination 1: 3514
IP Address 1, Destination 2: 3522
IP Address 2, Destination 2: 3530
Default: 0
Selections: 0, 1, 3, 5, 7
Enter This Data Digit to Select Options
Alternate Communication Options 0 1 2 3 4 5 6 7 8 9 10
11
12
13
14
15
No Alternate Communication
Enable Alternate Communication
Enable Anti-Replay
Use ARC Acks
Reserved
Enable Alternate Communication: Select this option to enable network communication. You must enter at least one IP
address as a routing destination. See
IP Address 1 (2) for Destination 1 (2) on page 112 for more information.
Enable Anti-Replay: Anti-replay prevents unauthorized messages from being sent to the ARC and being recognized as
having originated from the control panel. Enable this option to use the anti-replay procedure. To use this option, make sure
“Include IP Address” is enabled in
Network Interface Module Options on page 115.
Use ARC Acks: If this option is enabled, the control panel waits for an acknowledgment (Ack) from the ARC before sending
a second message. If this option is disabled, the control panel waits approximately 120 seconds between sending messages
(disable only for special applications).
Remote Programming Callback Number Alternate Communication Options
Address: 3538
Default: 0
Selections:
0 = No Alternate Communication
1 = Enabled Alternate Communication
If an IP address is entered into the Remote Programming Callback Number addresses (Addresses 0181-0212), RPS can be
used to program the control panel over an Ethernet network.
Select “1” if an IP address is entered in the Remote Programming Callback Number addresses.