EasyManua.ls Logo

Bosch DS7220V2 - 66.0 Standby Battery Calculation

Bosch DS7220V2
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 136 P/N: 4998152533-02 Copyright 2007 Bosch Security Systems, Inc. DS7200V2-UK Installer's Guide
PART V: REFRENCE MATERIALS
66.0 Standby Battery Calculation
A
AC Power On
Normal Current
B
AC Power Off
Minimum Current
C
In Alarm
Maximum Current
Model
Number
Quantity
Used
Each
Unit
1
Total Each
Unit
Total Each
Unit
Total
DS7240V2/
DS7220V2
85 x 1 =
85 85 x 1 = 85 120 x 1 =
120
Keypads:
DS7445i/
DS7445V2
35 x Qty =
35 x Qty = 115 x Qty =
DS7447E/
DS7447V2
100 x Qty =
100 x Qty = 100 x Qty =
Accessories:
DX2010 35 x Qty =
35 x Qty = 35 x Qty =
DX3010 10 x Qty =
10 x Qty = 10 x Qty =
DX3020 10 x Qty =
10 x Qty = 10 x Qty =
DX4010i/
DX4010
25 x Qty =
25 x Qty = 25 x Qty =
DX4020 84/110
2
x Qty =
84/110
2
84/110
2
x Qty = 84/110
2
84/110
2
x Qty =
84/110
2
RF3227E 30 x Qty =
30 x Qty = 30 x Qty =
Sounders Connected to PO 2:
D118 8
Speaker
0 x Qty =
0 x Qty = 330 x Qty =
Ratings of Other Devices in System that are not Shown Above:
x Qty =
x Qty = x Qty =
x Qty =
x Qty = x Qty =
x Qty =
x Qty = x Qty =
x Qty =
x Qty = x Qty =
x Qty =
x Qty = x Qty =
Total A =
Total B = Total C =
1
Currents shown in milliamperes (1 ampere = 1,000 milliampere)
2
84 mA max, 80 mA nominal 10 Base-T ; 110 mA max, 100 mA nominal 100 Base-T
Use the following formula to calculate standby battery capacity for 24 hours of standby power :
(Total B ____ x 24 hrs) + (Total C ____ x 0.067 hrs) + 10% reserve = Total battery Ah required
If the Column C total exceeds 1.2 A, then an external power supply is required.