Page 94 P/N: 4998152533-02 Copyright 2007 Bosch Security Systems, Inc. DS7200V2-UK Installer's Guide
PART IV: CONTROL PANEL PROGRAMMING
Configuring Steady, Pulse and One Shot Mode
Steady and Toggle Modes: These modes are not affected by the Time Base and Time Multiplier parameters below.
Pulse Modes: The system calculates the On Time (activation) and the Off Time for outputs based on the values in the Base
and Multiplier columns (see
Table 34). The duration, or On Time, of an output is determined by selecting one of the four
Base options from
Table 34. Calculate the Off Time by multiplying the Base by the Multiplier.
The Time Base of 200 ms in Table 34 and Table 35 is only available for on-board outputs.
Base On Time
(On Time = Time of Base)
Multiplier Off Time
(Off Time = Base x Multiplier)
Tolerance
0 0 N/A Always Off N/A
1 (200 ms) 200 ms 01-99 200 ms – 19.8 sec ±200 ms
2 (1 sec) 1 sec 01-99 1 – 99 sec ±1 sec
3 (1 min) 1 min 01-99 1 – 99 min ±1 min
4 (1 hr) 1 hr 01-99 1 – 99 hr ±1 hr
Table 34: Pulse Mode Configuration
One Shot Modes: The duration of the On Time of a One Shot output is determined by multiplying the Base by the Multiplier.
Base Multiplier On Time
(On Time = Base x Multiplier)
Tolerance
0 N/A 0 N/A
1 (200 ms) 01-99 200 ms – 19.8 sec ±200 ms
2 (1 sec) 01-99 1 sec – 99 sec ±1 sec
3 (1 min) 01-99 1 min – 99 min ±1 min
4 (1 hr) 01-99 1 hr – 99 hr ±1 hr
Table 35: One Shot Mode Configuration