Greensource CDi Series SM
Greensource CDi Series SM Model8733819578 (2019/02)
28 | Unit Configuration
Subject to change without prior notice
UNIT CONFIGURATION
Bosch EasyStart App
The Bosch EasyStart app is a digital interface that
allows access to information from the Heat Pump
Controller (HPC) making commissioning,
configuring, and troubleshooting easier. This
application is available in the Google Playstore, the
Apple App Store, as well as the Bosch Pro HVAC
website (www.boschprohvac.com). Search for
“Bosch EasyStart” in the appropriate store for your
device to download and launch the app. Once
launched, navigate through the legal information,
and then the user guide displays, explaining how to
connect the App and the heat pump, as well as
how to explore the features of the Bosch EasyStart
app.
The Bosch EasyStart app will only work on the
following devices: Android tablets with Android 4.0
operating system or higher, Apple iPads with iOS 8
or higher, and Windows 7.0 or higher laptops/PCs.
Settings
The Bosch EasyStart app is used to configure the
available features of the HPC as follows:
Table 3 HPC Settings
For more information refer to the website list in
the Bosch EasyStart app’s Installation,
Operation, and Maintenance Manual (IOM).
HPC Settings Default Settings
Freeze Protection Strategy 15°F–26°F 26°F
Cooling CFM per TON 300–450 400 CFM/Ton
Heating CFM per TON 300–450 375 CFM/Ton
Fan Only CFM reduction 50–100% 80%
Dehumidification CFM reduction 15–40% 15%
Heat Recover Package Enabled or Disabled Disabled
Heat Recovery Setpoint 110°F–140°F 120°F
Heat Recovery Sample Rate 2–6 Samples/Hr 3 Samples/Hr
Electric Heat Size None, 5kW, 10kW, 15kW, 20kW None
Low Loop Water Protection Enabled or Disabled Disabled
Low Loop Control Setpoint 20°F–50°F 34°F
Loop Pump Compressor Delay 30–240 seconds 30s
Mode of Compressor Operation Comfort or Economy Comfort
Down-Staging Latched or Unlatched Unlatched
Number of Lockouts 2–4 Strikes 3 Strikes
Lockout Reset (Y1) signal or (R) (Y1)
Units of Temperature °F or °C °F
Alarm Type Constant or Pulse Pulse
Date MM/DD/YYYY
Time HH:MM
High Efficiency Mode Enable or Disabled Disabled
Compressor Runtime Reset Write Only
Model Number (from the Unit Data Plate)
SM036-1VTC-FRTADC-
CMGXXXXXD7HXXX4XXXXSNA
Serial Number (from the Unit Data Plate) 1234-567-891011-1213141516