Supervision
The IP Audio Interface contains detectors for supervision of various functions of the device.
This way internal or external failures, disconnections or short circuits can be detected. Faults
are reported via the Fault Relay and can be passed to partner devices.
Figure 6.8: Supervision screen (default)
Max. Internal temperature
Default: 80 °C
Enter the threshold for the Maximum Internal Temperature. If the set value is exceeded, a
Temperature Fault is generated and shown on the Status page, see Status page, page 39.
Min. Backup PWR voltage
Default: 0
Enter the value for the Minimum Backup Power Voltage.
If the voltage drops below the set value, a fault is generated and shown on the Status page,
see Status page, page 39.
Remote Supervision Period
Default: 0 seconds
Enter a value in the range 0 – 255 seconds. This is the time between consecutive pings to
supervised partners (checked as such in the Partner Table, see Partner Table, page 20).