EasyManua.ls Logo

Bosch rexroth ctrlX DRIVE - Page 16

Bosch rexroth ctrlX DRIVE
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9) Mains input L1, L2, L3; For use on a solidly grounded wye
source only.
10) Copper wire; PVC-insulation (conductor temperature 75 °C;
T
a
≤ 40 °C) in accordance with NFPA 79 chapter 12 and
UL 508A chapter 28
11) Depending on switching frequency which was set in parameter
P‑0‑0001
Tab. 2-4: UL ratings and dimensions
UL ratings and dimensions (XMS*-W0054 … 0280)
Description Symbol Unit
XMS*-
W0054
XMS*-
W0070
XMS*-
W0090
XMS*-
W0100
XMS*-
W0120
XMS*-
W0210
XMS*-
W0250
XMS*-
W0280
Listing in accordance with UL
standard
UL 61800-5-1
Listing in accordance with CSA
standard
C22.2 No. 274-17
UL‑Files E134201
Pollution degree 2
Ambient temperature range
with nominal data
T
amax
°C 40
Mass m kg 4.25 6.2 18.9
Device height
1)
H mm 309
Device depth
2)
T mm 196.5
Device width
3)
B mm 75 125 250
Minimum distance on the top of
the device
4)
d
top
mm 80
Minimum distance on the bot‐
tom of the device
5)
d
bot
mm 80
Horizontal spacing at the de‐
vice
6)
d
hor
mm
0 (for devices of the ctrlX DRIVE product group in the DC bus group
(central supply))
1.5 (for devices of the ctrlX DRIVE product group outside of the DC
bus group (individual supply))
10 (for everything else (control cabinet wall, other devices, etc.))
Rated control voltage input
7)
U
N3
V 24
Rated control current input
8)
I
N3
A 4.3 6.4
Short circuit current rating SCCR A rms 42000
Rated input voltage, power
9)
U
LN_nom
V DC 254 ... 750
Rated input current
I
LN
A
DC
29.4
DC
38.2
DC
49.1
DC 73 DC 77
DC
153
DC
161
DC
180
Field wiring material (material;
conductor temperature; class)
Cu; 60/75 °C; 1
Output voltage
U
out
V AC 0 … 500
12/43
Ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02