26/48 Commissioning
Bosch Rexroth AG, HEDE 10-3X, RE 30277-02-B/07.2016
8.2.2 Explanation of menu level 1
SP1/rP1 Upper/lower limit value for system pressure, at which OUT1
switches with hysteresis setting.
Prerequisite: OUT1 setting is [Hno] or [Hnc]
FH1/FL1 Upper/lower limit value for system pressure, at which OUT1
switches with window setting.
Prerequisite: OUT1 setting is [Fno] or [Fnc]
EF Extended functions / opening of menu level 2.
8.2.3 Explanation of menu level 2
rES Restore factory setting.
ou1 Output function for OUT1:
Switching signal for the pressure limit values: hysteresis
function [H ..] or window function [F ..], either normally
open [. no] or normally closed [. nc].
ou2 Output function for OUT2:
Analog output for current system pressure: 4...20 mA [I] or
0...10 V [U]
dS1 Set delay for OUT1.
dr1 Reset delay for OUT1.
uni
Standard unit of measurement (display):
[bAr] / [PSI] / [MPA].
Lo Minimum value memory for system pressure.
Hi Maximum value memory for system pressure.
dAP Damping of the switching point.
dAA Damping of the analog output
coLr
Assignment of the display colors “red” and “green” within
the measuring range.