Commissioning 31/48
RE 30277-02-B/07.2016, HEDE 10-3X, Bosch Rexroth AG
8.5 Setting the output signals
8.5.1 Setting the output functions
▶ Select [ou1] and set the switching function:
– [Hno] = hysteresis function/NO,
– [Hnc] = hysteresis function/NC,
– [Fno] = window function/NO,
– [Fnc] = window function/NC.
▶ Select [ou2] and set the analog function:
– [I] = current signal 4...20 mA,
– [U] = voltage signal 0...10 V,
8.5.2 Determining the switching limits for the hysteresis
function
▶ [ou1] has to be set as [Hno] or [Hnc].
▶ Select [SP1] and set the value at which the output is set.
▶ Select [rP1] and set the value at which the output is
reset.
rP1 is always smaller than SP1. The unit only accepts values
which are smaller than the value for SP1.
8.5.3 Determining the switching limits for the window
function
▶ [ou1] has to be set as [Fno] or [Fnc].
▶ Select [FH1] and set the upper limit value.
▶ Select [FL1] and set the lower limit value.
FL1 is always smaller than FH1. The unit only accepts values
which are smaller than the value for FH1.