32/48 Commissioning
Bosch Rexroth AG, HEDE 10-3X, RE 30277-02-B/07.2016
8.6 Usersettings(optional)
8.6.1 Setting the delay for the switching outputs
[dS1] = set delay for OUT1.
[dr1] = reset delay for OUT1.
Select [dS1] or [dr1] and set a value between 0 and 50 s
(with 0 the delay time is not active).
For this unit, the parameters [dS1] and [dr1] for the set and
reset points are executed strictly according to the VDMA
guideline!
8.6.2 Setting damping for the switching signal
Select [dAP] and set the damping constant in seconds
(T value: 63 %); setting range 0.000...4.000 s.
Damping [dAP] has an inuence on the switching point/process
data ow (IO-Link communication) and the display.
8.6.3 Setting damping for the analog output
Select [dAA] and set the damping constant (10...90 %
rise time) in seconds; setting range 0.000...4.000 s.
Damping [dAA] only has an inuence on the analog output / the
analog signal path.