44/48 Troubleshooting
Bosch Rexroth AG, HEDE 10-3X, RE 30277-02-B/07.2016
Display
Status
LED OUT1
F = fault
W = warning
Type of fault Corrective measures
S.Loc W Setting buttons locked
via parameterization
software. Parameter
change is rejected (→
see page 29).
Unlocking only possible
via IO-Link interface
/ parameter setting
software.
OL W Process value too high
(measuring range
exceeded)
Check / increase system
pressure / select unit
with corresponding
measuring range.
UL W Process value too low
(below measuring
range)
Check / increase system
pressure / select unit
with corresponding
measuring range.
Err
ash-
es
F Internal fault /
malfunction
Contact the
manufacturer
*
)
The output remains deactivated as long as the excessive current /
short-circuit persists