4 Technical Data
4.1
IndraControl L45/L65/L85
Processor
CML45.1: AMD LX800 with 500 MHz
CML65.1: Intel Celeron M with 1.0 GHz
CML85.1: Intel Core2Duo with 1.2 GHz
RAM
Min. 256 MByte DRAM and min. 256 kByte RDS
1)
(see
chapter 9 "Ordering Information" on page 67).
Optional:
8 MByte SRAM - battery buffered
(for support refer to the System Description)
Interfaces:
Interface to function
modules
Bosch Rexroth PC104
Plus
Interface to I/O terminals Rexroth Inline interface
Communication interfa‐
ces
1 x Ethernet connection (RJ 45, 10Base-T, 100Base-
TX)
Optional:
1 x SERCOS III master-slave interface
Optional:
1 x PROFIBUS DP master-slave interface
2 x Ethernet connection (RJ 45, 10Base-T, 100 Base-
TX) for TCP/IP or RT Ethernet (PROFINET RT or
EtherNet/IP)
Ready Contact 1 x single-pin ready contact
Inputs and outputs 8 electrically isolated digital inputs
8 electrically isolated digital outputs
Weight 1.8 kg
Degree of protection IP 20
4.2 Voltage Supply
The
IndraControl L45/L65/L85 is supplied with 24 V. The following values of the
operating voltage comply with DIN EN 61131-2:
1)
RDS - Remanent Data Storage
Remanent data is automatically written to the Compact Flash card after loss of volt‐
age and is restored after rebooting the control.
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
Bosch Rexroth AG 19/81
Technical Data

Table of Contents