LED D Meaning
Off 24 V voltage is missing.
Green 24 V voltage is present.
Red Short-circuit or overload
Fig.7-19: LED D
Destruction of the device due to improper con‐
nection
NOTICE
If connected improperly, the device might be destroyed. For that reason, avoid:
Polarity reversal with simultaneous short-circuit of the output lines
Polarity reversal with simultaneous connection of externally polarized
suppressor diodes
Applying an external voltage > UB
The 0 V reference of the connected loads must be returned to the 0 V connec‐
tion of the IndraControl L45/L65/L85, i. e. a two-pin connection must be ensur‐
ed. Otherwise, there will be no reliable protection from GND breakage.
7.4 Interfaces
7.4.1 Ethernet Interface
X7E5 Ethernet network connection
Connector X7E5 can be used to connect the IndraControl L45/L65/L85 to an
Ethernet network.
The connection requirements defined for 100BaseTX in IEEE 802.3 are appli‐
cable.
RJ45, female connector, 8-pin
Type Ethernet 100Base TX
Cable length 100 m max.
Cable type CAT5e with S/STP
Transmission rate 10 or 100 MBit/s
max. 100 m
1
8
2
1
3
4
5
6
7
8
Ethernet RJ45
Ethernet
to the network
Fig.7-20: Ethernet interface
Bosch Rexroth recommends the use of a STP cable of category 5.
This port is intended for the programming device network!
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
Bosch Rexroth AG 43/81
Connections and Interfaces