Settings in the service menu
47
Worcester 2000 – 6 721 814 551 (2019/09)
8.2.3 Menu 3
Press the ( key and * key at the same time until L.1 appears.
Press arrow key until L.3 is displayed.
To confirm the selection: press OK key.
Selecting and setting the service function.
The basic settings are depicted as highlighted in the following table.
Table 23 Menu 3: factory settings
Service function Settings/adjustment range Remark/restriction
3-b1 Maximum approved heat output GC2000iW 25 C : 50 … 80 %
GC2000iW 30 C : 50 … 68 %
Set heat output in percent.
Measure gas flow rate.
Compare measured result with the setting
tables ( page 77). Correct the setting in
the case of any deviation.
3-b2 Time interval between stopping and
starting the burner in heating mode
3 … 10 … 60 minutes The time interval specifies the minimum waiting
time between switching on the burner and
switching it on again.
If a weather-compensated heating controller is
connected, this setting is optimised by the
heating controller.
3-b3 Temperature interval for switching the
burner off and back on
-15 … -6 … -2 K ( °C) The difference between the current flow
temperature and the set flow temperature until
the burner is switched on.
If a weather-compensated heating controller is
connected, this setting is optimised by the
heating controller.
3-C1 Maximum released DHW output 50 … 100 % On natural gas devices:
Set heat output in percent.
Measure gas flow rate.
Compare measured result with the setting
tables ( page 77). Correct the setting in
the case of any deviation.
3-C4 Turbine signal delay 2 … 16 × 0.25 seconds The delay prevents sudden changes in the water
supply pressure from causing the burner to
briefly operate although no water is drawn off.
3-C5 Delay of DHW mode (solar mode) 0 (not active) ... 50 seconds DHW mode will be suppressed until the DHW
temperature sensor detects that the water
preheated by solar energy has reached the
desired DHW temperature.
Set the DHW mode delay according to the
system conditions.
3-C6 Time interval between stopping and
restarting the burner for DHW heating
(only in comfort mode and summer
mode)
0 … 30 minutes After DHW is drawn off, the DHW heating
remains disabled for this period.
3-C8 Thermal disinfection up to draw-off
point
OFF: switched off
ON: switched on
If too much water is drawn off, the required
temperature may not be reached.
Only draw off enough water to allow the DHW
temperature of 70 °C to be reached.
Perform thermal disinfection
( Instructions for the user).
3-CA DHW mode 0: comfort mode, the device is continually kept at
the set temperature.
1: ECO mode, only heat-up to the selected
temperature when hot water is being drawn.
2: (not available)
3: (not available)
Short waiting time in comfort mode, when
domestic hot water is extracted. The device
therefore switches on, even if no domestic hot
water is extracted.
3-d6 Overrun time of the heating pump in
heating mode
1 … 3 … 60 minutes
61: 24 hours
The pump overrun begins at the end of the heat
demand by the heating controller.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Worcester GC2000iW 30 C NG and is the answer not in the manual?

Bosch Worcester GC2000iW 30 C NG Specifications

General IconGeneral
BrandBosch
ModelWorcester GC2000iW 30 C NG
CategoryBoiler
LanguageEnglish

Related product manuals