Fault finding and diagnosis
Worcester 2000 – 6 721 814 551 (2019/09)
64
11.2 Table of operation and fault displays
Fault
code
Fault
category
Description Remedy
200 O The device is in central heating mode.
201 O The appliance is in DHW mode.
202 O The appliance is in optimised switching mode:
the interval for restarting the burner has not yet
expired ( service function 3-b2).
203 O The appliance is on standby, there is no heat
demand.
204 O The current flow temperature is higher than the
set flow temperature. The burner has been
switched off.
207 Operating pressure too low. Fill and vent the system, check the system for leaks.
Replace pressure sensor if necessary.
208 O The appliance is in chimney sweep mode.
Chimney sweep mode is deactivated
automatically after 30 minutes.
212 Temperature increase for safety or flow
temperature sensor too fast.
Open the shut-off valves.
214 V The fan stops during the safety time. Check fan, replace if necessary.
Check mains voltage.
215 V Fan too fast. Replace fan.
Mains voltage must correspond to the default value.
Check PCB and fan harness, replace if necessary.
224
224
B
V
Flue gas temperature limiter or heat exchanger
temperature limiter has tripped.
If the blocking fault persists for a prolonged period, it becomes a locking fault.
Check position of isolation valve in heating circuit, open if required.
Check water pressure, if necessary top up until the preset pressure is reached.
Check the temperature limiter and connecting lead of the heat exchanger for
breaks, replace if required.
Check the flue gas temperature limiter and the connecting lead for breaks, replace
if required.
Vent appliance with service function 4-A1 ( page 48).
227
227
B
V
No flame detected. After the 5th ignition attempt, the blocking fault becomes a locking fault.
Check whether the gas isolator is open.
Check the gas supply pressure.
Check ionisation signal.
Check the power supply.
Check the electrodes with cable, replace if required.
Check the flue system, clean or repair if required.
Check gas/air ratio, adjust if necessary.
Clean heat exchanger.
Check the gas valve, replace if required.
Check burner setting, correct if necessary.
228 V Flame signal is present although burner is
switched off.
Check if there is a flame present.
Check electrodes and connecting leads, replace if required.
Check the gas valve, replace if required.
Check appliance electronics, replace if necessary.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Worcester GC2000iW 30 C NG and is the answer not in the manual?

Bosch Worcester GC2000iW 30 C NG Specifications

General IconGeneral
BrandBosch
ModelWorcester GC2000iW 30 C NG
CategoryBoiler
LanguageEnglish

Related product manuals