UNIT START-UP
1. Set the thermostat to the highest setting.
2. Set the thermostat system switch to “COOL”, . The
reversing valve solenoid should energize. The
compressor should not run.
3. Reduce the thermostat setting approximately 5
degrees below the room temperature.
4. Verify the water temperature is operating in the
cooling mode.
5. Turn the thermostat system switch to the “OFF”
position. The unit should stop running and the
reversing valve should de energize.
6. Leave the unit off for approximately (5) minutes to
allow for system equalization.
7. Turn the thermostat to the lowest setting.
8. Set the thermostat switch to “HEAT”.
9. Increase the thermostat setting approximately 5
degrees above the water temperature.
10. Verify the heat pump is operating in the heating
mode.
11. Set the thermostat to maintain the desired water
temperature.
12. Check for vibrations, leaks, etc.
MAINTENANCE
An annual “checkup” is required by a licensed
refrigeration mechanic. Recording the performance
measurements of volts, amps, and water temperature
differences (both heating and cooling) is recommended.
This data should be compared to the information on the
unit’s data plate and the data taken at the original
startup of the equipment.
INFORMATION ON DECOMMISSIONING
Only Trained and qualified technicians are allowed to
decommission and dispose of equipment following
applicable requirements and local codes.
Protecting the Environment
Components
Many parts in the Heat Pump can be fully recycled in the
end of the product life. Contact your city authorities for
information about the disposal of recyclable products.
Refrigerant
At the end of the service life of this appliance and prior
to it's environmental disposal, a person qualified to
work with refrigerant circuits must recover the
refrigerant from within the sealed system.
WARNING: Decommissioning of this
equipment can be hazardous due to system
pressure and electrical components. Only
trained and qualified personnel should
install, repair, or service the equipment.
By disposing of this product correctly you
will help ensure that the waste undergoes
the necessary treatment, recovery and
recycling-thus preventing potential negative
effects on the environment and human
health which could otherwise arise due to
inappropriate waste handling.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch WT Series and is the answer not in the manual?

Bosch WT Series Specifications

General IconGeneral
BrandBosch
ModelWT Series
CategoryHeat Pump
LanguageEnglish

Related product manuals