63
S Low Cool Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Cool Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
6.4.5. Heat Pump Heating
The heat pump heating mode can be exercised with this menu option. W i t h a 2--stage
heat pump, a Low Heat and a High Heat Run Time are independent l y select abl e to
exercis e.
For variabl e speed heat pumps, you can select the speed at which the heat pump will
exercis e.
For 18VS heat pumps, you can select the stage at which the heat pump wil l exercis e.
Duri ng the checkout, the stage and time can be changed by pressi ng the Change button
on the checkout status scr een.
After the selections are made, touch START.
NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting
and are independent of other airflow settings. To view airflows for normal air
conditioning cooling mode, exit the CHECKOUT screen and apply a heating
demand to the system.
S Low Heat Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Heat Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S Speed (variable speed heat pump only): Select abl e from low est available to 100%
d Default = lowest available as specified by variable speed heat pump
S Defrost: Yes or No (For Geothermal Heat Pumps, this option is not available.)
d Default = No