BTU VENTILATION CORPORATION OFFICE 888-884-8070 FAX 218-346-7485
www.btucorp.com
XT-70 Control Panel 73
Refrigeration records:
The refrigeration records are laid out in the same CSV file as
the XT records. There can be up to ten devices and can be
cut and paste to match up to the system. All cards must be in
order, starting with Card 1. Below each card, identify the
card type. 1 = CR-110 and 2 = ER-110 (required).
The numbers will set the order in which the values will
appear.
Once the file is set as desired, then save it as a CSV file and
use a name that references the given panel. Now upload the
new file to the XT panel. Generally, when changes are made
to this file, the records should be cleared.
[CARD_1]
1
Discharge Pressure 1
Suction Pressure 2
Suction Super Heat 3
Amps 0
Output 4
Mode 5
Lead Compressor 6
Suction Temp 7
Discharge Temp 0
[CARD_2]
1
Discharge Pressure 1
Suction Pressure 2
Suction Super Heat 3
Amps 0
Output 4
Mode 5
Lead Compressor 6
Suction Temp 7
Discharge Temp 0
[CARD_3]
2
Suction Press A 5
Suction Temp A 6
Suction Press B 7
Suction Temp B 8
Super Heat SP 2
Super Heat A 3
Super Heat B 4
Valve pos A 9
Valve pos B 10
Mode 1
Mode A 0
Super Heat SP B 0
Super Heat SP A 0
Mode B 0