Additional programming options
8
Logamatic 4323 - Subject to technical modifications.
53
The display shows the set value.
Release the "Temp" key to save your input.
To enter the next switching point (e. g. Friday, 13:00, 21 °C), repeat the
procedure detailed above.
Press "Back" to return to the permanent display.
New switch.point
Friday
17°C
at 10:00
USER NOTE
You cannot just enter an arbitrary temperature here. The factory-set day
and night setback temperatures are available, which can be modified
(Æ
Chapter 6.4).
USER NOTE
Only after all three details (day/time/temperature) have been defined for the
new switching point will it be automatically saved under "Own program" and the
heating circuit number (here: "2"). This saving is not shown on the display. The
display shows the blank screen "New switch.point" for the next switching point.
New switch.point
--------------
----
at ---