Additional programming options
8
Logamatic 4323 - Subject to technical modifications.
64
8.4 Creating a new DHW circulation pump program
You may operate the DHW circulation pump either according to the factory
settings "Program select. by heat. circs" or according to your own new switching
program "Program select. own CP".
If your circulation pump is to work independently of the heating circuits, you can
enter your own new DHW circulation pump program as follows:
Example:
The DHW circulation pump is to run on all weekdays from 06:30 to 09:00.
z Select a heating circuit (Æ Chapter 7.6).
(here: "DHW circulation")
z Select a program for the heating circuit "DHW circulation" (Æ Chapter 7.10).
(here: "Program select. new")
The display shows a blank screen "New switch.point" for the new switching
point.
z Enter the switching points (Æ Chapter 8.2).
Your DHW circulation pump will now operate according to your "Own program CP".
You can call up your new "Own program CP" by pressing "Prog" and turning the
rotary selector.
USER NOTE
With the factory setting "Program select. by heat. circs", the DHW circulation
pump is run 30 minutes prior to the first switching point of all heating circuits
associated with this control unit, and ends when the last heating circuit is
switched off.
New switch.point
--------------
----
at ---
USER NOTE
Only after all three details (day/time/temperature) have been defined the new
switching point will be automatically saved under "Own program CP" and the
heating circuit number "DHW circulation". The saving function is not visualised
on the display. The display shows a blank screen "New switch.point" for the
next switching point. Repeat this process for all required switching points.