36
Operating and functions
Determine the fitting K factor using a teach-in procedure depending on a volume ("TEACH F.")
The device will use the new K factor as soon as "SAVE YES" is confirmed when leaving the Parameters
menu.
Charge the pipe.
Wait for the flow rate to be stable.
confirm "TEACH F.": "MEASURE \" is displayed.
REtURN
K-FACtOR K=10.000
tEACh V.
0......9
The device calculates the K factor of the fitting and displays
it.
mEAsURE \
0.000 L/s
VALiD N/Y
tEACh F.
OUtPUt
K=2.8500
Enter the value of the flow rate in the pipe (value
between 0,001 and 9999). Confirm.
The device calculates the mean flow rate in the pipe, during
approximately 50 s.
The display shows the K factor of the fitting, may it have been entered
or determined by a teach-in procedure.
Confirm the displayed value.
confirm the K factor determined through teach-in or not.
Fig. 31: Teach-in procedure depending on the flow rate
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.