50
Operating and functions
Filter Response time Filter Response time
0 1 s 5 8 s
1 2 s 6 15 s
2 3 s 7 28 s
3 4 s 8 70 s
4 5 s 9 145 s
Filter 0: measured
flow rate
Filter 3 Filter 6 Filter 9
slow
fast
Fig. 49: Available filters
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.
8.6.14. Resetting both totalizers
This parameter makes it possible to reset both totalizers.
Both totalizers are reset upon confirmation of "SAVE YES" when leaving the Parameters menu.
tOtAL REsEt N
FREqUENC.
0......9
Choose to reset both totalizers or not.
Confirm
REsEt Y
Fig. 50: Diagram of the "TOTAL" parameter of the Parameters menu
The daily totalizer can be reset from the Process level or via the digital input.
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.