Maintenance and troubleshooting
9.5.3. Resolution of problems without message generation and
device status LED green
Device
status
LED
Current
output
AO1
Output DO1
and/or DO2
and/or DO3
Possible cause Recommended action
green 4-20 mA depending on
the thresholds or
switched
1)
he device does not properly
measure the flow rate.
→ Check that the K factor corre-
sponds to the fitting used.
→ Check that the Kw coefficient has
not been disturbed.
→ Carry out a teach-in procedure
to determine the K factor of the
fitting used.
green 4-20 mA depending on
the thresholds or
switched
1)
The displayed flow rate is not
nil but the flow rate in the pipe
is.
→ Check that the flow rate in the
pipe is nil.
→ Check that there are no bubbles in
the pipe.
→ Check the filter chosen.
→ Calibrate the flow zero point.
green 4-20 mA depending on
the thresholds or
switched
1)
The displayed flow rate is
always nil.
→ Check that the flow rate in the
pipe is not nil.
→ Check that the K factor or the Kw
coefficient are not too low.
→ Check that the electrodes are per-
pendicular to the flow direction.
→ Choose a smaller flow rate unit or
increase the number of displayed
decimals..
green 4-20 mA depending on
the thresholds or
switched
1)
The displayed flow rate is not
stable.
→ Check that there is fluid in the pipe.
→ Choose a higher filter.
green 4-20 mA depending on
the thresholds or
switched
1)
The displayed flow rate
changes very slowly.
→ Check that there is fluid in the pipe.
→ Choose a lower filter.
1)
If the output is configured to switch when a warning message is generated. See chap. 8.6.5.
English
Type 8045