31
Manual SOFTENER A27-A6X code P0011144 - Rev 3 - 09/02/2017
English
Step n° Display Purpose Action
0
PASSW ?
00
Enter the password to go through the advanced set-
ting.
êé to change
OK to con! rm
çM to cancel
1
PROP R
On
Enable / disable the proportional regeneration (the
Scope of Delivery sheet speci! es the integration of
this function in the softener).
ê to turn on / off
OK to con! rm
çM to cancel
2
CAPA
80
Modify the softening capacity of the device, which has
been automatically set once the resin volume was se-
lected (step 3 of regular setting).
êé to change
OK to con! rm
çM to cancel
3
CONSU
71
Adjust the water consumption per full regeneration.
Only for devices with the salt level follow-up by smart-
phone app.
êé to change
OK to con! rm
çM to cancel
4
SALT
2000
Adjust the salt consumption per full regeneration.
Only for devices with the salt level follow-up by smart-
phone app.
êé to change
OK to con! rm
çM to cancel
5
VOL OK
8 56
Volume of softened water (read only info). Here: 856
liters.
çM to go to next step
6
PEAKFL
10 68
Peak fl ow recorded since the last regeneration (read
only info). Here: 1068 liters per hour.
çM to go to next step
7
N REGE
48
Number of regenerations done since the commissioning.
May be reset.
êé to change
OK to con! rm
çM to cancel
8
CHLOR
Off
Enable / disable the chlorination function
êé to change
OK to con! rm
çM to cancel
9
ALARME
Off
Salt lack alarm enabled / disabled
êé to change
OK to con! rm
çM to cancel
10
SAFE L
2 50
Safe level value = remaining capacity value which trig-
gers the regeneration once reached.
êé to change
OK to con! rm
çM to cancel
11
REGE T
2:00
Time of regeneration start.
êé to change
OK to con! rm
çM to cancel
12
PRESS
4
Water network pressure. To be set for proportional re-
generation purpose.
êé to change
OK to con! rm
çM to cancel
13
FUL RG
5
Frequency of the full regenerations (to prevent from
loss of capacity occurring with time), for the softeners
with proportional regeneration function. Here: one full
regeneration every 5 regenerations.
êé to change
OK to con! rm
çM to cancel
14 STEPS
Setting of each regeneration step durations.
The followings step durations can be adjusted (one
submenu for each): Backwash (BACKW) ; aspiration
(ASPI) ; fast rinse (FAST) ; brine preparation (propor.
regen.) (BRINE) ; tank re! ll (propor. regen.) (REFILL)
OK to enter the menu,
otherwise çM then
êé to change
OK to con! rm
çM to cancel
15
FORCED
NONE
Turn ON or OFF the automatic forced regeneration after
a long time without water consumption
êé to activate
OK to con! rm
çM to cancel
16
RESET
OFF
Reset back on initial factory settings
êé to turn ON
OK to con! rm (twice)
çM to cancel