25
ENG
“humiSonic ventilation” +0300063EN - rel. 1.0 - 16.02.2016
Screen index Display description Def Min Max UOM
Gf01 Manual management
Manual mode No No Yes -
Gf02 Manual mode
Fill Off Off On Off ¦ On
Drain Off Off On Off ¦ On
Gf03 Manual mode
Mist 1 No No Yes No ¦ Yes
Mist 2 No No Yes No ¦ Yes
Tab. 6.h
6.9 Probe calibration
Once the control (regulation) type has been selected, the probes can
be calibrated by setting the off set. The delay for activation of the probe
alarm can also be set.
Screen index Display description Def Min Max UOM
Fa04 Regulation
Ambient probe (AI7)
Probe type: 0 to 1V ¦ 0 to 5V ¦ NTC
Off set 0.0 -100.0 100.0 -
Min 0.0 0.0 100.0 -
Max 100.0 0.0 100.0 -
Alarm delay 0 0 999 s
Fa05 Regulation
Ambient probe (TH)
Type rH%+T
Off set 0.0 -20.0 50.0 -
Fa06 Regulation
Limit probe (AI6)
Probe type: 0 to 1V ¦ 0 to 5V
Off set 0.0 -100.0 100.0 -
Min 0.0 0.0 100.0 -
Max 100.0 0.0 100.0 -
Alarm delay 10 0 999 s
Tab. 6.i
Input
A
Min
0
100%
Max
0%
Req
Fig. 6.a
Key
Input Input signal Min Input value for min. request
Req Request Max Input value for max request
AOff set
6.10 Access management
The delay after which the Service password (PW1) is requested can be
set, and quick access (Quick menu) to the parameters via the Set point
and On/Off icons disabled (see chap. “User interface”). In addition, a new
password can be set, and the main password PW0 enabled to access any
screen in the programming menu, not only the Service parameters.
Screen index Display description Def Min Max UOM
Gec01 Access management
Password delay 1 0 30 min
Gec02 Access management
Quick menu Yes No Yes -
Main menu password No No Yes -
Gec03 Access management
Insert new main menu
password (PW0)
0000 0000 9999 -
Gec04 Access management
Insert new service
password (PW1)
0000 0000 9999 -
Tab. 6.j
6.11 Settings
These parameters are set in the event of special needs:
1. to fi lter an excessive number of requests over a certain period, and
avoid numerous starts and stops, enter a longer start delay;
2. if there is no water, it may be useful to extend the delay time before
restarting, to avoid a premature no water alarm;
3. the alarm relay can be normally open (N.O.) or normally closed (N.C.);
the solenoid valve in standby can be set as open or closed;
4. the “drain delay in standby” time is only set if the drain solenoid valve
is selected as open in standby. This determines in delay for opening
the drain solenoid valve after switching to standby. It is useful in the
event of frequent starts/stops, to minimise the time needed to reach
steady operation.
Screen index Display description Def Min Max UOM
Fc01 Settings
Start delay 10 s 0 120
Restart wait 10 min 1 60
Alarm relay logic N.O. N.O. N.C. -
Fc03 Settings
Drain valve in stand-by Open Open Closed -
Drain delay in stand-by 0 min 60 min
Tab. 6.k
6.12 Network settings
The RS485 serial card (accessory) needs to be installed on the control
board in the “Master” panel. The network parameters need to be set in
the event of connection to a serial network. All the controllers in the
network must be set with the same protocol and communication speed
parameter. By enabling serial control, the humidifi er parameter can be set
over the serial connection.
Screen index Display description Def Min Max UOM
Gd01 BMS confi guration
Protocol Modbus Modbus Carel -
Speed 19200 1200 19200 bps
Address 1 1 207 -
Gd02 BMS confi guration
Serial manager Disabled Disabled Enabled -
Tab. 6.l