Table 5 — 23XRV Dimensions Heat Exchanger Sizes 30-57 (Nozzle-In-Head Waterbox)
*Assumes both cooler and condenser nozzles on same end of chiller.
NOTES:
1. Service access should be provided per American Society of Heating, Refrigerating, and Air-Conditioning Engineers
(ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.
2. Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.
3. Certified drawings available upon request.
4. Marine waterboxes may add 6 in. (152 mm) to the width of the machine. See certified drawings for details.
5. ‘A’ length dimensions shown are for standard 150 psig (1034 kPa) design and Victaulic connections. The 300 psig (2068 kPa)
design and/or flanges will add length. See certified drawings.
6. Dished head waterbox covers not available for 3 pass design.
Table 6 — 23XRV Heat Exchanger Sizes 30-57 Dimensions (Marine Waterbox)
*Assumes both cooler and condenser nozzles on same end of chiller.
†1 or 3 pass length applies if cooler is a 1 or 3 pass design.
NOTES:
1. Service access should be provided per American Society of Heating, Refrigerating, and Air-Conditioning Engineers
(ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.
2. Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.
3. Certified drawings available upon request.
4. Marine waterboxes may add 6 in. (152 mm) to the width of the machine. See certified drawings for details.
5. ‘A’ length dimensions shown are for standard 150 psig (1034 kPa) design and Victaulic connections. The 300 psig (2068 kPa)
design and/or flanges will add length. See certified drawings.
HEAT EXCHANGER
SIZE
A (LENGTH, WITH NOZZLE-IN-HEAD WATERBOX)
B (WIDTH) C (HEIGHT)1-PASS 2-PASS* 3-PASS
ft-in. mm ft-in. mm ft-in. mm
30 TO 32 14- 3
1
/
4
4350 13- 8
1
/
4
4172 14- 3
1
/
4
4350
See unit
certified
drawings
35 TO 37 15-11
3
/
4
4870 15- 4
3
/
4
4693 15-11
3
/
4
4870
40 TO 42 14- 9 4496 14- 3
1
/
8
4347 14- 6 4420
45 TO 47 16- 5
1
/
2
5017 15-11
5
/
8
4867 16- 2
1
/
2
4940
50 TO 52 14-10 4521 14- 4
1
/
2
4382 14- 6
1
/
2
4432
55 TO 57 16- 6
1
/
2
5042 16- 1 4902 16- 3 4953
HEAT EXCHANGER
SIZE
A (LENGTH, MARINE WATERBOX)
B (WIDTH) C (HEIGHT)
2-PASS* 1 OR 3-PASS†
ft-in. mm ft-in. mm
30 TO 32 14- 9 4496 16- 4
3
/
4
4997
See unit
certified
drawings
35 TO 37 16- 5
1
/
2
5017 18- 1
1
/
4
5518
40 TO 42 15- 2
3
/
4
4642 16- 3
1
/
4
5086
45 TO 47 16-11
3
/
4
5163 18- 4
3
/
4
5607
50 TO 52 15- 3
1
/
2
4661 16- 8
1
/
2
5093
55 TO 57 17- 0 5182 18- 5 5613
C
FRAME R COMPRESSOR 3’ - 0 (915mm)
RECOMMENDED OVERHEAD SERVICE CLEARANCE
2 MIN
(610 mm)
(WIDEST POINT)
4 - 10 MIN
(1219 mm)
A
MOTOR SERVICE
CLEARANCE
1 - 10 (559 mm)
TUBE REMOVAL
SPACE FOR
EITHER END
SIZES 30-32, 40-42,
50-52
12-7½ (3848 mm)
SIZES 35-37, 45-47,
55-57
14-4 (4369 mm)
B
4-10
0-3”
0-3”
0-5
SERVICE AREA
Fig. 14 — 23XRV Heat Exchanger Sizes 30-57 Dimensions (Unit with R Compressor Shown)