22
Table 18 — 23XRV Waterbox Cover Weights, Frames A/B — English (lb)
LEGEND NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is
included in the heat exchanger weights shown in Tables 11-13.
Table 19 — 23XRV Waterbox Cover Weights, Frames A/B — SI (kg)
LEGEND NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is
included in the heat exchanger weights shown in Tables 11-13.
RIG MACHINE COMPONENTS — Refer to Fig. 15-27 and
Carrier Certified Prints for machine component disassembly.
NOTE: Label each wire before removal when wiring must be
disconnected (see Fig. 15 and 16). Clip all wire ties necessary
when removing pressure and temperature sensors. Disconnect
all pressure transducer wires at the sensor. Temperature sensors
cannot be disconnected from their cables; remove temperature
sensors from their thermowells and label as required.
WATERBOX
DESCRIPTION
COOLER FRAMES A AND B CONDENSER FRAMES A AND B
VICTAULIC
NOZZLES
FLANGED
VICTAULIC
NOZZLES
FLANGED
NIH,1-Pass Cover 150 psig
217 244 242 274
NIH,2-Pass Cover 150 psig
172 265 191 298
NIH,3-Pass Cover 150 psig
228 245 261 277
NIH/Marine Plain End, 150 psig
157 157 173 173
MWB Cover, 150 psig
296 296 332 332
NIH,1-Pass Cover 300 psig
217 271 242 312
NIH,2-Pass Cover 300 psig
172 301 191 334
NIH,3-Pass Cover 300 psig
228 263 261 295
NIH/Marine Plain End, 300 psig
157 157 173 173
MWB Cover, 300 psig
296 296 332 332
NIH —
Nozzle-in-Head
MWB —
Marine Waterbox
WATERBOX
DESCRIPTION
COOLER FRAMES A AND B CONDENSER FRAMES A AND B
VICTAULIC
NOZZLES
FLANGED
VICTAULIC
NOZZLES
FLANGED
NIH,1-Pass Cover 1034 kPa
98 111 110 124
NIH,2-Pass Cover 1034 kPa
78 120 87 135
NIH,3-Pass Cover 1034 kPa
103 111 118 126
NIH/Marine Plain End, 1034 kPa
71 71 78 78
MWB Cover, 1034 kPa
134 134 151 151
NIH,1-Pass Cover 2068 kPa
98 123 110 142
NIH,2-Pass Cover 2068 kPa
78 137 87 151
NIH,3-Pass Cover 2068 kPa
103 119 118 134
NIH/Marine Plain End, 2068 kPa
71 71 78 78
MWB Cover, 2068 kPa
134 134 151 151
NIH —
Nozzle-in-Head
MWB —
Marine Waterbox
IMPORTANT: Only a qualified service technician
should perform this operation.
WARNING
Do not attempt to disconnect flanges while the machine is
under pressure. Failure to relieve pressure can result in per-
sonal injury or damage to the unit.
CAUTION
Before rigging the compressor, disconnect all wires enter-
ing the power panel.