20
Table 13 — 23XRV Code 30-57 Heat Exchanger Weights
*Rigging weights are for standard tubes of standard wall thickness (Turbo-B3 and Spikefin 2, 0.025-in. [0.635 mm] wall).
NOTES:
1. Cooler includes the suction elbow and
1
/
2
the distribution piping weight.
2. Condenser includes float valve and sump, discharge stub-out, and
1
/
2
the distribution piping weight.
3. For special tubes refer to the 23XRV Computer Selection Program.
4. All weights for standard 2-pass NIH (nozzle-in-head) design with Victaulic grooves.
Table 14 — 23XRV Additional Data for Cooler Marine Waterboxes*
*Add to heat exchanger data for total weights or volumes.
NOTES:
1. Weight adder shown is the same for cooler and condenser of equal frame size.
2. For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volume).
CODE
ENGLISH SI
DRY RIGGING WEIGHT
(lb)*
MACHINE CHARGE
DRY RIGGING WEIGHT
(kg)*
MACHINE CHARGE
COOLER
ONLY
CONDENSER
ONLY
REFRIGERANT
WEIGHT (lb)
LIQUID VOLUME
(Gal.)
COOLER
ONLY
CONDENSER
ONLY
REFRIGERANT
WEIGHT (kg)
LIQUID
VOLUME (L)
WITH
ECONOMIZER
WITHOUT
ECONOMIZER
COOLER CONDENSER
WITH
ECONOMIZER
WITHOUT
ECONOMIZER
COOLER CONDENSER
30 4148 3617 800 650 56 56 1877 1676 363 295 212 212
31 4330 3818 800 650 64 65 1959 1769 363 295 242 246
32 4522 4023 800 650 72 74 2046 1860 363 295 273 280
35 4419 4529 910 760 61 61 2000 2089 413 345 231 231
36 4627 4758 910 760 70 72 2094 2195 413 345 265 273
37 4845 4992 910 760 80 83 2193 2299 413 345 303 314
40 5008 4962 900 750 103 110 2675 2746 408 340 390 416
41 5178 5155 900 750 111 119 2758 2839 408 340 420 450
42 5326 5347 900 750 119 129 2832 2932 408 340 450 488
45 5463 5525 1015 865 112 120 2882 3001 460 392 424 454
46 5659 5747 1015 865 122 130 2976 3108 460 392 462 492
47 5830 5967 1015 865 130 141 3061 3214 460 392 492 534
50 5827 6013 1250 1100 132 147 3182 3304 567 499 500 556
51 6053 6206 1250 1100 143 156 3294 3397 567 499 541 590
52 6196 6387 1250 1100 150 165 3364 3485 567 499 568 625
55 6370 6708 1430 1280 144 160 3429 3620 649 581 545 606
56 6631 6930 1430 1280 156 171 3556 3726 649 581 590 647
57 6795 7138 1430 1280 164 181 3636 3826 649 581 621 685
HEAT EXCHANGER
FRAME, PASS
ENGLISH SI
RIGGING WEIGHT
(lb) (See Note 2)
WATER VOLUME
(Gal.)
RIGGING WEIGHT
(kg) (See Note 2)
WATER VOLUME
(L)
FRAME A,B, 1 PASS, 150 psig (1034 kPa) 760 64 345 242
FRAME A,B, 2 PASS, 150 psig (1034 kPa) 400 29 181 110
FRAME A,B, 3 PASS, 150 psig (1034 kPa) 752 55 341 208
FRAME 3, 1 AND 3 PASS, 150 psig (1034 kPa) 730 84 331 318
FRAME 3, 2 PASS, 150 psig (1034 kPa) 365 42 166 159
FRAME 4, 1 AND 3 PASS, 150 psig (1034 kPa) 1888 109 856 413
FRAME 4, 2 PASS, 150 psig (1034 kPa) 944 54 428 204
FRAME 5, 1 AND 3 PASS, 150 psig (1034 kPa) 2445 122 1109 462
FRAME 5, 2 PASS, 150 psig (1034 kPa) 1223 61 555 231
FRAME A,B, 1 PASS, 300 psig (2068 kPa) 812 64 368 242
FRAME A,B, 2 PASS, 300 psig (2068 kPa) 436 29 198 110
FRAME A,B, 3 PASS, 300 psig (2068 kPa) 788 55 357 208
FRAME 3, 1 AND 3 PASS, 300 psig (2068 kPa) 860 84 390 318
FRAME 3, 2 PASS, 300 psig (2068 kPa) 430 42 195 159
FRAME 4, 1 AND 3 PASS, 300 psig (2068 kPa) 2162 109 981 413
FRAME 4, 2 PASS, 300 psig (2068 kPa) 1552 47 704 178
FRAME 5, 1 AND 3 PASS, 300 psig (2068 kPa) 2655 122 1204 462
FRAME 5, 2 PASS, 300 psig (2068 kPa) 1965 53 891 201