APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
NOTE: This value is read or calculated by the controller and cannot
be changed from this item.
Operating Mode and Sub-Mode Directory
Alarms Mode and Sub-Mode Directory
SUB-MODE SUB-SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
OVR
SCHEDULE OVERRIDE
OVR.T X hrs Timed Override Hours
Range: 0 to 4
Default: 0
OVR.L X hrs Override Time Limit
Range: 0 to 4
Default: 0
SPT.O XX.X
ǻF (ǻC) Space Temperature Offset See Note
T.OVR YES/NO Timed Override
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
MODE
MODES CONTROLLING UNIT
MD05 ON/OFF Ramp Load Limited
MD06 ON/OFF Timed Override in effect
MD09 ON/OFF Slow Change Override
MD10 ON/OFF Minimum OFF time active
MD14 ON/OFF Temperature Reset
MD15 ON/OFF Demand Limited
MD17 ON/OFF Low Temperature Cooling
MD18 ON/OFF High Temperature Cooling
MDTG ON/OFF Time Guard Active
MD21 ON/OFF High SCT Circuit A
MD22 ON/OFF High SCT Circuit B
MD23 ON/OFF Minimum Comp. On Time
MD25 ON/OFF Low Sound Mode
D.OIL ON/OFF Digital Oil Recover Mode
L.OUT ON/OFF OAT Below Lockout Temp
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
CRNT
CURRENTLY ACTIVE ALARMS
AXXX
TXXX
PXXX
Expansion of the Pre-alert, Alert
or Alarm only
Alarms are shown as AXXX.
Pre-Alerts are shown as PXXX.
Alerts are shown as TXXX.
Up to 20 Alarms will be displayed.
RESET ALL CURRENT ALARMS
RCRN NO/YES Reset current alarms
HIST
ALARM HISTORY
AXXX
TXXX
PXXX
Expansion of the Pre-alert, Alert
or Alarm with Time and Date
Stamp
Alarms are shown as AXXX.
Pre-Alerts are shown as PXXX.
Alerts are shown as TXXX.
Up to 20 Alarms will be displayed.