EasyManua.ls Logo

Carrier 38APD130 - Configuration Tables; DISPLAY (Marquee Display Set Up)

Carrier 38APD130
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
202
APPENDIX B — CCN TABLES (cont)
Maintenance Tables (cont)
OCCDEFM/OCCPC01S
Configuration Tables
DISPLAY (Marquee Display Set Up)
HPA (Head Pressure Circuit A)
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
Current Mode (1=Occup.)
N
Range:
0 = Unoccupied
1 = Occupied
MODE Read Only
Current Occup. Period #
N
Range: 0 to 8
PER-NO Read Only
Timed-Override in Effect No/Yes OVERLAST Read Only
Timed-Override Duration
N
Range: 0 to 4
hours OVR_HRS Read Only
Current Occupied Time 00:00 to 23:59 STRTTIME Read Only
Current Unoccupied Time 00:00 to 24:00 ENDTIME Read Only
Next Occupied Day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
NXTOCDAY Read Only
Next Occupied Time 00:00 to 23:59 NXTOCTIM Read Only
Next Unoccupied Day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
NXTUNDAY Read Only
Next Unoccupied Time 00:00 to 23:59 NXTUNTIM Read Only
Previous Unoccupied Day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
PRVUNDAY Read Only
Previous Unoccupied Time 00:00 to 24:00 PRVUNTIM Read Only
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
Service Password
NNNN
Default: 1111
Range: 0000 to 9999
PASSWORD Read/Write
Password Enable
Disable/Enable
Default: Enable
PASS_EBL Read/Write
Metric Display
Off/On
Default: Off
DISPUNIT Read/Write
Language Selection
N
Range:
0 = English
1 = Espanol
2 = Francais
3 = Portugues
Default: 0
LANGUAGE Read/Write
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
SCT Delta for Comp A1 NNN.n 'F ('C) A1SCTDT Configuration
SCT Delta for Comp A2 NNN.n 'F ('C) A2SCTDT Configuration

Table of Contents