EasyManua.ls Logo

Carrier 38APD130 - C-TYP=5, Space Temperature Control Example

Carrier 38APD130
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74
Sequence of Operation
— The MBB monitors the space tem-
perature input together with the unit configurations to make a
determination of Control Point Run Status
o
VIEW
o
CTPT.
The control will call for a low cool set point, Setpoints
o
COOL
o
CSP.1 (Cooling Setpoint 1) or high cool set point
Setpoints
o
COOL
o
CSP.2 (Cooling Setpoint 2) depending on
the difference between the Space Temperature (Run Status
o
VIEW
o
SPT) and the space temperature set point (Set-
points
o
COOL
o
SPS.P). CSP.1 should be greater than CSP.2.
CSP.1 or CSP.2 will be used as the basis for the Active Set
Point (Run Status
o
VIEW
o
SETP) based on the configura-
tion settings, Low Cool On Set Point (Setpoints
o
COOL
o
L.C.ON), High Cool On Set Point (Set-
points
o
COOL
o
H.C.ON), and Low Cool Off Set Point (Set-
points
o
COOL
o
L.C.OF) to determine the control point.
If the Space Temperature rises above the SPS.P + L.C.ON,
the system will start with CSP.1 as the Control Point. Space
Temperature Control Mode (Run Status
o
VIEW
o
SPT.M)
will indicate 1 (Lo Cool). As long as the Space Temperature
does not rise above SPS.P + L.C.ON + H.C.ON, the unit will
continue to supply conditioned air with CSP.1 as the Control
Point until the Space Temperature falls below SPS.P + L.C.ON
L.C.OF. If the Space Temperature falls below SPS.P +
L.C.ONL.C.OF, mechanical cooling will cease. Space Tem-
perature Control Mode, SPT.M will indicate 0 (Cool Off). If
the Space Temperature rises above SPS.P + L.C.ON +
H.C.ON, the unit will change the Control Point to CSP.2.
Space Temperature Control Mode, SPT.M will indicate 2 (Hi
Cool). CSP.2 will remain the Control Point until the Space
Temperature falls below SPS.P + L.C.ON – (L.C.OF/2) at
which time the Control Point will change to CSP.1. CSP.1 will
remain the Control Point until the Space Temperature falls be-
low SPS.P + L.C.ONL.C.OF. Space Temperature Control
Mode, SPT.M will indicate 0 (Cool Off).
The following example illustrates this control scheme.
Given:
SPS.P = 72 F,
L.C.ON = 1,
H.C.ON = 3,
L.C.OF = 2 F,
CSP.1 = 60 F,
CSP.2 = 55 F
If Space Temperature equals 73 F (SPS.P + L.C.ON [Low
Cool On]) cooling will begin and the Control Point equals 60 F
(CSP.1). As long as Space Temperature does not exceed the
High Cool On setting (SPS.P
+
L.C.ON + H.C.ON), CSP.1
will remain the Control Point until the Space Temperature falls
below 71 F (SPS.P + L.C.ONL.C.OF [Low Cool Off])
when mechanical cooling will cease.
If space temperature rises above 76 F (SPS.P + L.C.ON +
H.C.ON [High Cool On]), control point set point changes to
55 F (CSP.2). CSP.2 will remain the Control Point until the
Space Temperature falls below 72 F (SPS.P + L.C.ON
L.C.OF/2 [High Cool Off]), control point transitions back to
60 F (CSP.1). If space continues to fall below 71 F (SPS.P +
L.C.ONL.C.OF [Low Cool Off]), the unit is shut off.
Figure 84 summarizes this example.
68.0 69.0 70.0 71.0 72.0 73.0 74.0 75.0 76.0 77.0
CSP.1
CSP.2
H.C.ON
L.C.ON
L.C.OF/2
L.C.OF
SPS.P
L.C.ON
Low Cool On
High Cool On
High Cool Off
Low Cool Off
°F
Fig. 84 — C-TYP=5, Space Temperature Control Example

Table of Contents

Related product manuals