EasyManua.ls Logo

Carrier 38APD130 - C.TYP=4 (Tstat 2 Stg) Wiring

Carrier 38APD130
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70
Fig. 82 — C.TYP=4 (Tstat 2 Stg) Wiring
AHU
THERMOSTAT
(REQUIRED)
REMOTE ON/OFF
DEMAND
LIMIT SIGNAL
4-20 mA
SIGNAL
GENERATOR
DEMAND LIMIT STEP 2
DEMAND LIMIT STEP 1
38AP LVT
TERMINAL STRIP
+
FS1
25
24
18
16
14
13
8
7
6
5
4
3
2
1
ALM
R
15
12
Y2
Y1
R
X
C
G
W2
W1
CXB-J6
(38APD070-130 ONLY)
FIELD-SUPPLIED
TRANSFORMER
(REQUIRED)
RED
7
6
5
PNK
ORN
LLSV-A2
LLSV-B2
24 VAC
SECONDARY
LLSV-B (38APD)
LLSV-A2 (38APS)
or LLSV-B2 (065)
LLSV-A
or LLSV-B (065)
LEGEND
NOTES:
1. Field wiring must be in accordance with local codes.
2. LVT-1 and 2 are for the alarm relay. The maximum load allowed for the alarm relay
is 5 VA sealed, 10 VA at 24 VAC. Field power supply is not required.
3. LVT-24, 25, and 2 are for control of field-supplied liquid line solenoid valve (LLSV)
15 VA sealed, 30 VA inrush at 24 VAC. Field power supply is not required.
4. For 38APD070-130 units, an additional LLSV, 15 VA sealed, 30 VA inrush at 24
VAC can be connected to CXB. A field-supplied control transformer is required, not
to exceed 75 VA.
5. All discrete inputs are 24 VAC.
6. Installation of fan status switch (FS1) is recommended. If not used, a jumper must
be installed.
7. Energy management module (EMM) is required for Demand Limit functions, 4 to
20 mA, Demand Limit Step 1 and 2, or 4 to 20 mA Temperature Reset.
8. This control scheme is valid for 38APD,APS025, 027 and 030. It is not recom-
mended for units with more than 2 compressors, 38APD040-130 and 38APS040-
065.
9. This control scheme does not support digital compressor operation.
10. The contacts for Remote On-Off, Fan Status Switch and Demand Limit must be
rated for dry circuit applications capable of handling a 24 VAC load up to 50 mA.
AHU Air-Handling Unit
ALM R Alarm Relay
CXB Compressor Expansion Board
FS1 Fan Status Switch
LLSV-A Liquid Line Solenoid, Circuit A, First Stage
LLSV-A2 Liquid Line Solenoid, Circuit A, Second Stage
(38APS040,050, 38APD070-130 only)
LLSV-B
Liquid Line Solenoid, Circuit B, First Stage
(38APS065, 38APD only)
LLSV-B2
Liquid Line Solenoid, Circuit B, Second Stage
(38APS065, 38APD070-130 only)
LVT Low Voltage Terminal
Factory Wiring
Field Wiring

Table of Contents

Related product manuals