225
APPENDIX E — CONTROL METHODS WITH INPUTS FOR CONTROL MODE COMPARISON
CTRL DESCRIPTION
ENABLE-
OFF-
REMOTE
SWITCH
OCCUPANCY
SCHEDULE
CHIL_S_S
VALUE
EMSTOP
VALUE
INDOOR FAN
STATUS
SWITCH
SPT
SATISFIED
(C.TYP=3
OR 5)
ALARM STAT
0 Switch Control
Enable N/A N/A
Enable Closed No No 5 (ON LOCAL)
Enable Closed Yes No 9 (SPT SATISFIED)
Enable Open Yes/No No 8 (IDFS NOT ON)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Off N/A N/A
Enable Closed/Open Yes/No No 1 (OFF LOCAL)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Remote-
Open
N/A N/A
Enable Closed/Open Yes/No No 1 (OFF LOCAL)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Remote-
Closed
N/A N/A
Enable Closed No No 5 (ON LOCAL)
Enable Closed Yes No 9 (SPT SATISFIED)
Enable Open Yes/No No 8 (IDFS NOT ON)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
2 Occupancy
Enable
Occupied N/A
Enable Closed No No 7 (ON TIME)
Enable Closed Yes No 9 (SPT SATISFIED)
Enable Open Yes/No No 8 (IDFS NOT ON)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Unoccupied N/A
Enable Closed/Open Yes/No No 3 (OFF TIME)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Off
Occupied N/A
Enable Closed/Open Yes/No No 1 (OFF LOCAL)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Unoccupied N/A
Enable Closed/Open Yes/No No 1 (OFF LOCAL)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Remote -
Open
Occupied N/A
Enable Closed/Open Yes/No No 1 (OFF LOCAL)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Unoccupied N/A
Enable Closed/Open Yes/No No 1 (OFF LOCAL)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Remote-
Closed
Occupied N/A
Enable Closed No No 7 (ON TIME)
Enable Closed Yes No 9 (SPT SATISFIED)
Enable Open Yes/No No 8 (IDFS NOT ON)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)
Unoccupied N/A
Enable Closed/Open Yes/No No 3 (OFF TIME)
Enable Closed/Open Yes/No Yes 4 (OFF EMRGCY)
EMSTOP Closed/Open Yes/No Yes/No 4 (OFF EMRGCY)