APPENDIX B — CCN TABLES (cont)
Service Table
SERVICE
Setpoint Table
SETPOINT
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
COMPRESSOR ENABLE
Enable Compressor A1
Default: Depends on Unit
Model. If Compressor Size
is greater than 0, value is
Enable.
ENABLEA1 Read/Write
Enable Compressor A2 ENABLEA2 Read/Write
Enable Compressor A3 ENABLEA3 Read/Write
Enable Compressor B1 ENABLEB1 Read/Write
Enable Compressor B2 ENABLEB2 Read/Write
Enable Compressor B3 ENABLEB3 Read/Write
Reverse Rotation Enable
Disable/Enable
Default: Enable
REVR_VER Read/Write
Two Comp Ckt Oil Mgmt
Disable/Enable
Default: Enable
TCOM_EBL Read/Write
DESCRIPTION VALUE UNITS POINT NAME
NETWORK
ACCESS
COOLING
Cooling Setpoint 1
NNN.n
Range: 40.0 to 80.0 (4.4 to 26.7)
Default: 60.0 (15.6)
°F (°C) CSP1 Read/Write
Cooling Setpoint 2
NNN.n
Range: 40.0 to 80.0 (4.4 to 26.7)
Default: 55.0 (12.8)
°F (°C) CSP2 Read/Write
Space T Cool Setpoint
NNN.n
Range: 65.0 to 80.0 (18.3 to 26.7)
Default: 78.0 (25.6)
°F (°C) SPT_SP Read/Write
Space Temperature Offset NN.n °F (°C) SPTO Read Only
Space T SP Plus Offset NNN.n °F (°C) SPSP_PO Read Only
Percent Cap. Requested NNN % PERCAP Read Only
Lo Cool On Setpoint
NN.n
Range: –1.0 to 2.0 (–0.6 to 1.1)
Default: 1.0 (0.6)
'F ('C) DMDLCON Read/Write
HI Cool On Setpoint
NN.n
Range: 0.5 to 20.0 (0.3 to 11.1)
'F ('C) DMDHCON Read/Write
Lo Cool Off Setpoint
NN.n
Range: 0.5 to 2.0 (0.3 to 1.1)
Default: 0.5 (0.3)
'F ('C) DMDLCOFF Read/Write
RAMP LOADING
Cooling Ramp Loading
N.n
Range: 0.2 to 2.0
Default: 1.0
CRAMP Read/Write
Head Setpoint ON
NNN.n
Default: 115.0 (46.1)
°F (°C) HSP_ON Read/Write
Head Setpoint OFF
NNN.n
Default: 72.0 (22.2)
°F (°C) HSP_OFF Read/Write
Fan On Set Point
NNN.n
Default: 105.0 (40.5)
°F (°C) FANONSP Read Only
Fan Off Set Point
NNN.n
Default: 55.0 (12.8)
°F (°C) FANOFFSP Read Only
Fan Stage Delta
NNN.n
Default: 15.0 (8.3)
'F ('
C) FSTGDLTA Read/Write
Fan Delta Active Time
NNN
Default: 60
sec FANDLTTM Read/Write
OAT Lockout Temperature
NNN.n
Range: –20.0 to 80 (–28.9 to 26.7)
Default: 30.0 (–1.1)
°F (°C) OATLOCK Read/Write