EasyManua.ls Logo

Carrier 58HDX - Indoor Combustion Air (Unconfined Space); Standard and Known-Air-Infiltration Rate Methods

Carrier 58HDX
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
d.
Vertical
duct
openings
or
openings
directly
communic-
ating
with
the
outdoors
require
1
square
inch
of
free
area
per
4,000
BTUH
(5.5
cm2/kW)
for
combined
in-
put
of
all
gas
appliances
in
the
space
(see
Table
1).
3.
When
one
permanent
outdoor
opening
is
used,
the
opening
requires:
a.
1
sq.
in
of
free
area
per
3,000
BTUH
(7
cm2/kW)
for
combined
input
of
all
gas
appliances
in
the
space
(see
Table
1)
and
b.
not
less
than
the
sum
of
the
areas
of
all
vent
connect-
ors
in
the
space.
The
opening
shall
commence
within
12”
(305
mm)
of
the
top
of
the
enclosure.
Appliances
shall
have
clearances
of
at
least
1”
(25
mm)
from
the
sides
and
back
and
6"
from
the
front.
The
opening
shall
directly
communicate
with
the
outdoors
or
shall
communicate
through
a
vertical
or
horizontal
duct
to
the
outdoors
or
spaces
(crawl
or
attic)
that
freely
communicate
with
the
outdoors.
4.
Combination
of
Indoor
and
Outdoor
Air
shall
have:
a.
Indoor
openings
that
comply
with
the
Indoor
Com-
bustion
Air
Method
below
and
b.
Outdoor
openings
located
as
required
in
the
Outdoor
Combustion
Air
Method
above
and
c.
Outdoor
openings
sized
as
follows.
(1.)
Calculate
the
Ratio
of
all
Indoor
Space
volume
divided
by
required
volume
for
Indoor
Combus-
tion
Air
Method.
(2.)
Outdoor
opening
size
reduction
Factor
is
1
minus
the
Ratio
in
1)
above.
(3.)
Minimum
size
of
Outdoor
openings
shall
be
the
size
required
in
Outdoor
Combustion
Air
Meth-
od
above
multiplied
by
reduction
Factor.
Table
1
Free
Area
BTUH
Minimum
Free
Area
Required
for
Each
Opening
or
Duct
to
Outdoors
Input
Two
Horizontal
Ducts
Single
Opening
Two
Vertical
Ducts
or
Open-
(cain.
/4.000
Rating
(sq.
in./2,000
BTUH)
(sq.
in./3,000
BTUH)
(eq,
in,/
4,600
BTUH)
TBTUH)
60,000
30
sq.
in.
(194
cm?)
20
sq.
in.
(129
cm?)
15 sq.
in.
(97
cm?)
5"
(127
mm)
80,000
40
sq.
in.
(258
cm?)
26.7
sq.
in.
(172
cm?)
20.0
sq.
in.
(129
cm2)
5"
(127
mm)
100,000
50
sq.
in.
(322
cm2)
33.3
sq.
in.
(215
cm2)
25
sq.
in.
(161
cm2)
6”
(152
mm)
EXAMPLE:
Determining
Free
Area
Furnace
Water
Heater
Total
Input
100,000
+
30,000
=
(130,000
+
4,000)
=
32.5
Sq.
In.
Vertical
Furnace
Water
Heater
Total
Input
100,000
+
30,000
=
(130,000
+
2,000)
=
65 Sq.
In.
Horizontal
Indoor
Combustion
Air
(Unconfined
Space)
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Most
homes
will
require
additional
air
from outdoors
for
combustion
and
ventilation.
A
space
with
at
least
50
cubic
feet
per
1,000
Btuh
(4.8
M?/kW)
Input
rating
or
homes
with
tight
construction
may
need
outdoor
air,
supplied
through
ducts,
to
supplement
air
infiltration
for
proper
combustion
and
ventilation
of
flue
gasses.
Standard
and
Known-
Air-
Infiltration
Rate
Methods
©
NFPA
&
AGA
Indoor
air
is
permitted
for
combustion
and
ventilation,
if
the
Standard
or
Known-Air-Infiltration
Rate
Method
is
used.
The
Standard
Method
may
be
used,
if
the
space
has
no
less
volume
than
50
cubic
feet
per
1,000
BTUH
(4.8
M3/kW)
input
rating
for
all
gas
appliances
installed
in
the
space.
The
standard
method
permits
indoor
air
to
be
used
for
combustion
and
ventilation
air.
The
Known
Air
Infiltration
Rate
Method
shall
be
used
if
the
infiltration
rate
is
known
to
be
less
than
0.40
air
changes
per
hour
(ACH)
and
equal
to
or
greater
than 0.10
ACH.
Infiltration
rates
greater
than 0.60
ACH
shall not
be
used.
The
minimum
required
volume
of
the
space
varies
with
the
number
of
ACH
and
shall
be
determined
per
Table
2
or
Equations
1
and
2.
Determine
the
minimum
required
volume
for
each
appliance
in
the
space,
and
add
the
volumes
together
to
get
the
total
minimum
required
volume
for
the
space.
4
WARNING
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to
supply
additional
air
by
means
of
ventilation
grilles
or
ducts
could
result
in
personal
injury
or
death.
An
unconfined
space
or
homes
with
tight
construction
may
not
have
adequate
air
infiltration
for
proper
combustion
and
ventilation
of
flue
gasses.
Most
homes
will
require
additional
air.
10

Other manuals for Carrier 58HDX

Related product manuals