EasyManua.ls Logo

Carrier 58HDX - Joining Pipe and Fittings; Fire Hazard; Horizontal Termination

Carrier 58HDX
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rubber
Coupling
___VentPipe
&
Clamps
;
A
(Top
Panel
Exit)
Vent
Pipe
NOTE:
The
90°
elbow
is
approved
for
use
inside
the
furnace
ONLY.
—_—
90°
Elbow
|
Vent
Fitting
a
&
Clamps
Combustion
Blower
‘aq Rotate
downward
xt:
to
10°
vind
\
[wos
:
AQ7714
Fig.
20
-
Proper
Sealing
Procedure
for
Combustion
Blower
Joining
Pipe
and
Fittings
SEE
VENT
AND
COMBUSTION
AIR
PIPING,
vent
and
Combustion
Air
Piping
Guidelines
in
this
manual
for
applicable
ASTM
Standards
for
vent
materials.
FIRE
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Observe
all
cautions
and
warnings
printed
on
material
containers.
Provide
adequate
ventilation
and
do
NOT
assemble
near
heat
source
or
open
flame.
Do
NOT
smoke
while
using solvent
cements
and
avoid
contact with
skin
or
eyes.
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Do
NOT
use
solvent
cement
that
has
become
curdled,
lumpy
or
thickened
and
do
NOT
thin.
Observe
precautions
printed
on
containers.
For
applications
below
32°F
(0°C),
use
only
low
temperature
type
solvent
cement.
Poor
joints
may
lead
to
disconnected
or
leaking
vent
pipe
joints
allowing carbon
monoxide
to
enter
the
living
space.
1.
Cut
pipe
end
square,
remove
ragged
edges
and
burrs.
Chamfer
end
of
pipe,
then
clean
fitting,
socket
and
pipe
joint
of
all
dirt,
grease,
or
moisture.
NOTE:
Stir
the
solvent
cement
frequently
while
using.
Use
a
natural
bristle
brush
or
the
dauber
supplied
with
the
cement.
The
proper
brush
size
is
one
inch.
2.
After
checking
pipe
and
socket
for
proper
fit,
wipe
socket
and
pipe
with
cleaner-primer.
Apply
a
liberal
coat
of
primer
to
inside
surface
of
socket
and
outside
of
pipe.
Do
NOT
allow
primer
to
dry
before
applying
cement.
3.
Apply
a
thin
coat
of
cement
evenly
in
the
socket.
Quickly
apply
a
heavy
coat
of
cement
to
the
pipe
end
and
insert
pipe
into
fittings
with
a
slight
twisting
movement
until
it
bottoms
out.
NOTE:
Cement
MUST
be
fluid
while
inserting
pipe.
If
NOT,
recoat
pipe.
4.
Hold
the
pipe
in
the
fitting
for
30
seconds
to
prevent
the
tapered
socket
from
pushing
the
pipe
out
of
the
fitting.
5.
Wipe
all
excess
cement
from
the
joint
with
a
rag.
Allow
15
minutes
before
handling. Cure
time
varies
according
to
fit,
temperature
and
humidity.
Connecting
Vent
Pipes
and
Termination
(Direct
Vent)
NOTE:
For
direct
vent
applications,
combustion
air
intake
and
vent
MUST
terminate
in
the
same
atmospheric
pressure
zone.
If
installation
is
in
a
cold
climate
(sustained
temperatures
0°F
(-18°C)and
below
for
24
or
more
consecutive
hours),
increase
the
minimum
distance
between
vent pipe
and
air
intake
from
8”
to
18”
(203
to
457
mm).
1.
Install
all
couplings,
nipples
and
elbows
using
proper
pro-
cedures
for
Joining
Pipe
and
Fittings
and
maintain
spa-
cing
between
vent
and
combustion
air
piping
as
indicated
in
Fig.
21
through
Fig.
23.
soe
MD
MAX
L
*18
in.
(457.2mm)
Minimum
for
.
So
cold
climates
(sustained
tem-
JA
peratures
O0"F(-
17°C)
and
below
Sh
for
24
or
more
consecutive
i
hours)
7
PL
8"
203.2mm)
|
MINS
.
A
EXHAUST
£7
m
12”
_
304.8mm)
“MIN.
<<
%
oY
\_
GRADE
LEVEL
OR
AO7715
Fig.
21
-
Sidewall
Termination
12”
(305
mm)
or
More
Above
Snow
Level
or
Grade
Level
Horizontal
Termination
1.
Cut
two
holes.
2-1/2"
(64
mm)
for
2”
(51
mm)
pipe,
3”
(76
mm)
for
2-1/5"
(64
mm)
pipe,
or
31,"
(89
mm)
for
3”
(76
mm)
pipe.
Do
NOT
make
the
holes
oversized,
or
it
will
be
necessary
to
add
a
sheet
metal
or
plywood
plate
on
the
outside
with
the
correct
size
hole
in
it.
2.
Check
hole
sizes
by
making
sure
it
is
smaller
than
the
couplings
or
elbows
that
will
be
installed
on
the
outside.
The
couplings
or
elbows
MUST
prevent
the
pipe
from
be-
ing
pushed
back
through
the
wall.
3.
Extend
vent
pipe
and
combustion
air
pipe
through
the
wall
3/4"
(19
mm)
to
1”
(25
mm)
and
seal
area
between
pipe
and
wall.
4.
Install
the
couplings,
nipple
and
termination
elbows
as
shown
and
maintain
spacing
between
vent
and
combustion
air
piping
as
indicated
in
Fig.
21
and
Fig.
22.
A
metal
shield
is
recommended
18”
x
18”
(457
mm
x
457
mm)
min.
or
18”
(457
mm)
min.
diameter
around
the
vent
termination
at
the
exterior
wall
to
protect
the
house
exterior
materials
from
flue
product
or
condensation
(freezing)
damage.
28

Other manuals for Carrier 58HDX

Related product manuals