EasyManua.ls Logo

Carrier 58HDX - Installation Requirements

Carrier 58HDX
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Aluminum
or
non-rusting
shield
recommended.
*8”
(208.2mm)
Min.
(See
Vent
Termination
Shielding
for
dimensions}.
1
Coupling
on
ends
of
20
(6.1m)
Max.
exhaust
pipe.
Total
insame
|
co
Inlet
Pipe
i;
|
pipe
&
coupling
out
i
Bo
oN
-
attnospherc
5
yf
(notused
on
/
|
side
structure
=
8”
a
ch
rede
ii
(208.2mm)
fee
See
mode
ios
t—
t
a
fl
[
LK
|
|
ir
t
l
q
=
Vent Pipes
MUST
be|
=
oO
supported
=
an
Horizontally
and
5
8
203.2mm)
Min.
Vertically
a
20'
(6.1m)
Max.
in
same
atmospheric
zone
*
Increase
minimum
from
8”
(203.2mm)
to
18”
(457.2mm)
for
cold
climates
(sus-
tained
temperatures
F
(-
17°
C)
and
below
for
24
or
more
consecutive
hours).
25-23-33
A07700
Fig.
1
-
Typical
Upflow
Installation
See
Vent
Termination
Coupl
insid
Shielding
in
Vent
Section.
OUpINg
Of
insice
\
and
outside
of
wall
to
festrain
vent
pipe
oe
(—
*”
Min,
(203
mm)
A\
;
Inlet
Pipe
20'
Max.
in
same
(6
M
ip
\
ae
(not
used
on
atmospheric
zone
:
j
8"
Min.
(203
mm)
Sole
Pipe
an
!
del)
;
model)
/
4
.
Vent
Pipes
MUST
“3
w!
*5"TMin,
(203
mm)
20)
Max.
(6.1
M)
in
|same
atmospheric
zone
be
supported
Horizon-
tally
and
Vertically
25-23-33a
*
Increase
minimum
from
8” to
18”
(203
to
457
mm)
for
cold
climates
(sustained
temperatures
O°F
(-18
°C)
and
)
below
for
24
or
more
consecutive
hours).
AQ7762
Fig.
2
-
Typical
Downflow
Installation
Installation
Requirements
1.
Install
furnace
level.
2.
This
furnace
is
NOT
to
be
used
for
temporary
heat
of
buildings
or
structures
under
construction.
3.
Install
furnace
as
centralized
as
practical
with
respect
to
the
heat
distribution
system.
4.
Install
the
vent
pipes
as
short
as
practical,
and
in
accordance
to
these
instructions.
(See
Vent
and
Combustion
Air
Piping
section).
5.
Maintain
clearance
for
fire
safety
and
servicing.
A
front
clearance
of
24"
(607
mm)
required
and
30”
(762mm)
recommended
for
access
to
the
burner,
controls
and
filter.
See
clearance
requirements
in
Fig.
4.
6.
Use
a
raised
base
for
upflow
furnace
if
the
floor
is
damp
or
wet
at
times.
7.
For
downflow
installations,
non
combustible
subbase
must
be
used
under
the
furnace
unless
installation
is
on
a
non
combustible
floor
surface.
This
requirement
applies
even
when
a
coil
box
or
cabinet
is
used.
8.
For
horizontal
installations,
line
contact
is
permissible
only
between
lines
formed
by
intersection
of
back
and
two
sides
of
furnace
jacket,
and
building
joists,
studs
or
framing.
9.
Residential garage
installations
require:
¢
Burners
and
ignition
sources
installed
at
least
18"
(457
mm)
above
the floor.
¢
Located
or
physically
protected
from
possible
damage
by
a
vehicle.
10.
Local
codes
may
require
a
drain
pan
under
the
entire
furnace
and
condensate
trap
when
the
furnace
is
installed
in
attic
application.
This
furnace
may
be
used
for
construction
heat
provided
that
all
the
following
conditions
are
met:
¢
The
furnace
is
permanently
installed
with
all
electrical
wiring,
piping,
venting
and
ducting
installed
according
to
these
installation
instructions.
A
return
air
duct
is
provided,
sealed
to
the
furnace
casing,
and
terminated
outside
the
space
containing
the
furnace.
This
prevents
a
negative
pressure
condition
as
created
by
the
circulating
air
blower,
causing
a
flame
rollout
and/or
drawing
combustion
products
into
the
structure.
The
furnace
is
controlled
by
a
thermostat.
It
may
not
be
“hot
wired”
to
provide
heat
continuously
to
the
structure
without
thermostatic
control.
Clean
outside
air
is
provided
for
combustion.
This
is
to
minimize
the
corrosive
effects
of
adhesives,
sealers
and
other
construction
materials.
It
also
prevents
the
entrainment
of
drywall
dust
into
combustion
air,
which
can
cause fouling
and
plugging
of
furnace
components.
The
temperature
of
the
return
air
to
the
furnace
is
maintained
between
55°
F
(13°
C)
and
80°
F
(27°
C),,
with
no
evening
setback
or
shutdown.
The
use
of
the
furnace
while
the
structure
is
under
construction
is
deemed
to
be
intermittent
operation
per
our
installation
instructions.
The
air
temperature
rise
is
within
the
rated
rise
range
on
the
furnace
rating
plate,
and
the
firing
rate
has
been
set
to
the
rating
plate
value.
The
filters
used
to
clean
the
circulating
air
during
the
construction
process
must
be
either
changed
or
thoroughly
cleaned
prior
to
occupancy.
The
furnace,
ductwork
and
filters
are
cleaned
as
necessary
to
remove
drywall!
dust
and
construction
debris
from
all
HVAC
system
components
after
construction
is
completed.
After
construction
is
complete,
verify
furnace
operating
conditions
including
ignition,
input
rate,
temperature
rise
and
venting
according
to
these
instructions.
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Do
NOT
operate
furnace
in
a
corrosive
atmosphere
containing
chlorine,
fluorine
or
any
other
damaging
chemicals,
which
could
shorten
furnace
life.
Refer
to
Combustion
&
Ventilation
Air
section,
Contaminated
Combustion
Air
for
combustion
air
evaluation
and
remedy.

Other manuals for Carrier 58HDX

Related product manuals