EasyManua.ls Logo

Carrier 58HDX - Applicable ASTM Standards for Vent Materials; Sizing Combustion Air and Vent Pipe

Carrier 58HDX
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Applicable
ASTM
Standards
for
Vent
Materials
Cell
Solvent
Materials
sn
~
e.
R
Core
|
Fittings
|
Primer
P P
Pipe
Cement
D2468
ABS
D1527
__
F628
&
--
D2235
D2661
D2466
PVC
D1785
|
D2241
|
F891
&
F656
|
D2564
D2665
CPVC
F444
F442
--
F438
--
F493
ABS
to
PVC
-- -- -- -- --
D3138
NOTE:
1.
In
Canada,
all
pipe,
fittings
&
cements
must
conform
to
applicable
CSA
standards
or
to
local
codes
having
juris-
diction.
2.
Only
use
solvent
cements
that
are
marked
for
use
with
the
specific
venting
material.
3.
ABS
to
PVC
transition
joints
REQUIRE
a
special
solvent
cement
that
meets
the
requirements
of
ASTM
D3138.
4.
Refer
to
ASTM
D2855
for
general
procedure
to
use
for
cementing
plastic
pipe
and
fittings.
NOTE:
In
order
to
create
a
seal
that
allows
future
removal
of
pipe,
RTV
sealant
MUST
be
used
on
the
inlet
pipe
where
it
joins
to
the
furnace.
NOTE:
AI!
vent
piping
MUST
be
installed
in
compliance
with
local
codes
or
ordinances,
these
instructions,
good
trade
practices,
and
codes
of
country
having
jurisdiction.
1.
Determine
the
best
routing
and
termination
for
the
vent
pipe
and
air
inlet
pipe
by
referring
to
all
of
the
instructions
and
guidelines
in
this
Section.
2.
Determine
the
size
required
for
the
vent
pipe
and
air
inlet
pipe.
3.
Loosely
assemble
all
venting
parts
without
adhesive
(pipe
joint
cement)
for
correct
fit
before
final
assembly.
4.
Furnace
shall
be
installed
so
as
to
prevent
the
accumula-
tion
of
condensate.
5.
Use
of
vertical
piping
is
preferred
because
there
will
be
some
moisture
in
the
flue
gases
that
may
condense
as
it
leaves
the
vent
pipe
(See
Instructions
For
Horizontal
Vents).
6.
The
vertical
vent pipe
MUST
be
supported
so
that
no
weight
is
allowed
to
rest
on
the
combustion
blower.
7.
Exhaust
vent
piping
or
air
inlet
piping
diameter
MUST
NOT
be
reduced.
8.
All
exhaust
vent
piping
from
the
furnace
to
termination
MUST
slope
upwards.
A
minimum
of
!/4”
(6
mm)
per
foot
of
run
is
required
to
properly
return
condensate
to
the
fur-
nace
drain
system.
9.
Use
DWV
type
long
radius
elbows
whenever
possible,
as
they
provide
for the
minimum
slope
on
horizontal
runs
and
they
provide
less
resistance
in
the
vent
system.
If
DWV
elbows
cannot
be
used,
use
two,
45°
elbows
when
pos-
sible.
On
horizontal
runs
the
elbows
can
be
slightly
mis-
aligned
to
provide
the
correct
slope.
10.
All
horizontal
pipe runs
MUST
be
supported
at
least
every
five
feet
with
galvanized
strap
or
other
rust
resistant
ma-
terial.
NO
sags
or
dips
are
permitted.
11.
All
vertical
pipe
runs
MUST
be
supported
every
six
feet
where
accessible.
12.
The
minimum
pipe
run
length
is
2’
(.6
M).
13.
The
piping
can
be
run
in
the
same
chase
or
adjacent
to
supply
or
vent
pipe
for
water
supply
or
waste
plumbing.
It
can
also
be
run
in
the
same
chase
with
a
vent
from
another
90+
furnace.
NOTE:
In
NO
case
can
the
piping
be
run
in
a
chase
where
temperatures
can
exceed
140°
F
(60°
C).
or
where
radiated
heat
from
adjacent surfaces
would
exceed
140°
F
(60°
C).
14.
The
vent
outlet
MUST
be
installed
to
terminate
in
the
same
atmospheric
pressure
zone
as
the
combustion
air
in-
let.
15.
The
vent
system
can
be
installed
in
an
existing
unused
chimney
provided
that:
¢
Both
the
exhaust
vent
and
air
intake
run
the
length
of
the
chimney.
¢
No
other
gas
fired
appliance
or
fireplace
(solid
fuel)
is
vented
into
the
chimney.
¢
The
top
of
the
chimney
MUST
be
sealed
flush
or
crowned
up
to
seal
against
rain
or
melting
snow
so
ONLY
the
piping
protrudes.
¢
The
termination
clearances
shown
in
Fig.
7
and
8
are
maintained.
16.
Furnace
applications
with
vertical
vents
requiring
vent
dia-
meter
increaser
fittings
must
have
increaser
fittings
in-
stalled
in
vertical
portion
of
the
vent.
Condensate
will
be
trapped
in
the
vent
if
the
vent
diameter
is
increased
prior
to
having
an
elbow
turned
upward.
This
could
cause
nuis-
ance
tripping
of
the
pressure
switch.
Combustion
Air
and
Vent
Piping
Insulation
Guidelines
NOTE:
Use
closed
cell,
neoprene
insulation
or
equivalent.
If
Fiberglass
or
equivalent
insulation
is
used
it
must
have
a
vapor
barrier.
Use
R
values
of
7
up
to
10’,
(2.1
-
3.0
M)
R-II
if
exposure
exceeds
10".
If
Fiberglass
insulation
is
used,
exterior
to
the
structure,
the
pipe
MUST
be
boxed
in
and
sealed
against
moisture.
1.
When
the
vent
or
combustion
air
pipe
height
above
the
roof
exceeds
30"(762
mm),
or
if
an
exterior
vertical
riser
is
used
on
a
horizontal
vent
to
get
above
snow
levels,
the
ex-
terior
portion
MUST
be
insulated.
2.
When
combustion
air
inlet
piping
is
installed
above
a
sus-
pended
ceiling,
the
pipe
MUST
be
insulated
with
moisture
resistant
insulation
such
as
Armaflex
or
other
equivalent
type
of
insulation.
3.
Insulate
combustion
air
inlet
piping
when
run
in
warm,
hu-
mid
spaces.
Sizing
Combustion
Air
and
Vent
Pipe
Consult
Table
3
to
select
the
proper
diameter
exhaust
and
combustion
air
piping.
Exhaust
and
combustion
air
piping
is
sized
for
each
furnace
BTUH
size
based
on
total
lineal
vent
length
(on
inlet
or
outlet
side),
and
number
of
90°
elbows
required.
Two
45°
elbows
can
be
substituted
for
one
90°
elbow.
The
elbow
or
elbows
used
for
vent
termination
outside
the
structure
ARE
counted,
including
elbows
needed
to
bring
termination
above
expected
snow
levels.
The
elbow
inside
the
furnace
on
the
58HDX
IS
NOT
included
in
the
count.

Other manuals for Carrier 58HDX

Related product manuals