EasyManua.ls Logo

Carrier 58HDX - Changing Blower Speed; Electrical Shock Hazard; Reduced Furnace Life Hazard; FURNACE MAINTENANCE

Carrier 58HDX
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
To
check
temperature
rise,use
the
following
procedure:
1.Place
thermometers
in
supply
and
return
air
registers
as
close
to
furnace
as
possible,
avoiding
direct
radiant
heat
from
heat
exchangers.
2.Operate
furnace
continuously
for
15
minutes
with
all
registers
and
duct
dampers
open.
3.Take
reading
and
compare
with
range
specified
on
rating
plate.
4.If
the
correct
amount
of
temperature
rise
is
NOT
obtained,
it
may
be
necessary
to
change blower
speed.
A
higher
blower
speed
will
lower
the
temperature
rise.
A
lower
blower
speed
will
increase
the
temperature
rise.
Changing
Blower
Speed
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Turn
OFF
power
to
furnace
before
changing
speed
taps.
NOTE:
The
speed
taps
that
the
manufacturer
sets
from
the
factory
for
this
product
are
based
on
a
nominal
400
CFM
per
ton
cooling
and
the
basic
mid
range
on
the
temperature
rise
for
heating.
Since
the
manufacturer
cannot
establish
the
static
pressure
that
will
be
applied
to
the
unit,
it
is
the
responsibility
of
the
installer
dealer/contractor
to
select
the
proper
speed
taps
for
the
application
when
the
unit
is
installed.
If
it
is
necessary
to
change
speeds,
refer
to
steps
below.
REDUCED
FURNACE
LIFE
HAZARD
Failure
to
follow
this
caution
may
result
in
reduced
furnace
life.
Use
ONLY
the
blower
motor
speed
taps
insert
indicated
in
the
Circulation
Air
Blower
Data
for
setting
air
temperature
rise.
Table
8
Blower
Speed
Chart
Wire
Color
Motor
Speed
Black High
Orange*
Med—High
Blue
Medium
Red
Low
*
Med—High
speed
may
not
be
provided
on
all
models.
1.
Refer
to
Furnace
Wiring
Diagram
for
location
of
the
heat-
ing
and
cooling
speed
taps
located
on
the
furnace
control
as
well
as
location
of
unused blower
motor
speed
leads.
Use
the
chart
(Table
8)
to
determine
the
blower
motor
speed
settings.
2.
Change
the
heat
or
cool
blower
motor
speed
by
removing
the
motor
lead
from
the
“Heat”
or
“Cool”
terminal
and
replace
it
with
the
desired
motor
speed
lead
from
the
“Unused
Motor
Lead”
location.
Connect
the
wire
previ-
ously
removed
from
the
“Heat”
or
“Cool”
terminal
to
the
vacated
“Unused
Motor
Lead”
terminal.
3.
If
the
same
speed
must
be
used
for
both
heating
and
cool-
ing,
remove
the
undesired
motor
speed
lead
from
the
“Heat”
or
“Cool”
terminal
and
connect
that
lead
to
the
open
terminal
at
“Unused
Motor
Lead”
location.
Attach
a
jumper
between
the
“Heat”
and
“Cool”
terminals
and
the
remaining
motor
speed
lead.
NOTE:
For
motors
with
(4)
speed
leads,
it
will
be
necessary
to
tape
off the
terminal
of
the
motor
speed
lead
removed
from
the
“Heat”
or
“Cool”
terminal
with
electrical
tape
since
an
open
terminal
will
not
be
available
at
the
“Unused
Motor
Lead”
location.
Continuous-
Fan
Operation
using
“G”
Energizing
the
“G”
terminal
on
the
furnace
control
provides
continuous
fan
operation.
This
is
done
by
connecting
the
G
terminal
of
the
thermostat
to
the
G
terminal
on
the
furnace
control.
When
the
FAN
switch
is
turned
from
auto
to
ON
the
fan
will
operate
continuously
at
“HEAT”
speed.
EAC
will
be
energized
in
this
mode.
NOTE:
In
heating,
the
fan
will
turn
off
during
furnace
ignition
and
warm
up
then
restart
at
heating
speed.
Hard
Wired
Continuous
Fan
Operation
A
terminal
is
provided
on
the
furnace
control
board
located
in
the
circulating
blower
compartment
for
operation
of
the
continuous
fan
option.
This
connection
is
intended
for
the
low
speed
motor
tap,
and
has
a
lower
contact
rating
(8
amps)
than
the
heat
and
cool
taps.
When
the
low
speed
blower
lead
is
connected
to
this
terminal,
this
will
provide
low
speed
blower
operation
whenever
the
other
two
speeds
(Heat
or
Cool)
are
not
energized.
Thoroughly
check
the
system
after
modification
to
ensure
the
proper
operation
of
the
circulating
air
blower
in
all
modes
of
operation.
Separate
Speed
Selections
for
Heat,
Cool,
and
Continuous
Fan
Connect
low
speed
lead
from
circulating
motor
to
the
“Cont.”
terminal
at
the
furnace
control.
The appropriate
motor
leads
should
already
be
connected
to
the
“Heat”
and
“Cool”
terminals.
Heating
and
Continuous
Blower
Speed
the
Same
If
it
is
necessary
to
operate
the
heating
speed
and
continuous
blower
speed
using
the
same blower
speed,
connect
a
jumper
between
the
“Heat”
and
“Cont.”
terminals
on
the
furnace
control.
NOTE:
There
should
be
only
ONE
motor
lead
going
to
the
“Heat”
and
“Cont.”
terminals.
FURNACE
MAINTENANCE
FIRE,
EXPLOSION,
OR
CARBON
MONOXIDE
HAZARDS
Failure
to
follow
this
warning
could
result
in
personal
injury,
death
and/or
property
damage.
It
is
recommended
that
the
furnace
be
inspected
and
serviced
on
an
annual
basis
(before
the
heating
season)
by
a
qualified
service
technician.
42

Other manuals for Carrier 58HDX

Related product manuals