Installation and Programming Guide 123
Example
Programming Instructions for Actions
Goal
Create an action to monitor up to four input events and drive one output event (action
result).
Pre-conditions
Program the input and output events you want the Action to monitor or control.
Notes
See Aritech Reliance XR Reference Guide for more details on Actions.
Write/Plan out on paper what you want to create to make it easier to set up Actions and
associated settings.
Channel Group 1
Channel 1
Channel 4
Channel 6
Event List 1
Critical
Alarms
Bypass & Restore
AC Fail
AC Fail
Menu 6.11.1.1
Channel Group 1
System Event
Reporting
Channel 4
Control Room 2
Event List = 1
Next Channel = 5
Channel 6
Email
Event List = 2
Next Channel = 0
Channel 1
Control Room 1
Event List = 1
Channel Attempts = 3
Next Channel = 2
Menu 18 Channel Groups
System sends event to
Channel Group
Channel Group
sends event
to every Channel
it contains
Menu 5 Channels
Channel 5
Control Room 2
Event List = 1
Next Channel = 0
Channel 2
Control Room 1
Event List = 1
Channel Attempts = 3
Next Channel = 0
After failing Channel Attempts on the last back up channel, Aritech
Reliance XR will go back to the first Channel in the chain.
Sequence Attempts = 2
Channels 1 and 4 will attempt to send the event as AC Fail is on the
corresponding Event List. Back up channels 2 and 5 will also attempt to send
the event if they are used.
Channel 6 will NOT send the event as Event List 2 does not include AC Fail
events.
Menu 17 Event Lists
Event List 2
Informational
Open & Closes
Autotest
Event 1
Event 2
Event 3
Event 4
Action
State
and
or
=
Action
Result
and
or
and
or
+