32 Installation and Programming Guide
Getting Connected
Once your devices have been cabled and installed, there are four (4) ways to connect to the
Aritech Reliance XR system to perform programming:
Method 1: via UltraSync+ app this provides access to the built-in Web Server
via a smartphone app.
Method 2: via built-in Web Server All features can be accessed from a web
browser via drop-down and click-through menus. No software installation is
required. This allows access to most accessed features for basic programming.
Method 3: via DLX900 Management Software All features can be
programmed using a PC with Microsoft Windows 7, 8 and 10. DLX900 allows
easier programming of complex sites as the graphical interface can show all
options from multiple menus simultaneously.
Method 4: via on-site keypad - The NXX-1820- touchscreen offers a
programming menu for full system configuration. Refer to the NXX-1820-
Installation Manual. The Aritech Reliance XR Reference Guide will assist you in
navigating the menus.
Account Access
Note: Installer Account Disabled When Armed
If a non-engineer account arms the system at any time, engineer accounts will not be able
to log in, any current program mode will end, and this will be recorded in the event log. Ask
the end-user to disarm the panel and leave it disarmed so you can log in to program it.
Note: Remote Access May Require Level 2 User Authorization
Two remote access features “Enable Web Program” and “Always Allow DLX900” require an
authorized master (Level 2) user to enter their PIN code on an NXX-1820- keypad before
remote programming can be performed.
If either “Enable Web Program” or “Always Allow DLX900” have been disabled, ask a
Master User to press Menu, enter their PIN code on a keypad, then Settings. The panel will
now be in Program Mode, and you can use an engineer (Level 3) user such as “installer” to
perform programming via the web page, app, or DLX900.