LOW COOL LOCKOUT TEMPERATURE 
Range 
•  OFF - Functionality disabled. Cooling always starts with first stage compressor (Y1) 
and stages up to second stage (Y1 and Y/Y2) when the demand is sufficient and 
staging and cycle timer constraints have been satisfied. 
•  80° – 110°F - (5°F increments) Outdoor temperature above which both the first 
and second stages of the compressor are energized to satisfy all cooling demands. 
This check is performed when the first stage of the compressor is energized. If at the 
time the compressor is energized the outdoor air temperature is greater than or 
equal to the low cool lockout temperature, then the second stage of the compressor 
is energized also.  When a cycle starts under a low cool lockout condition, it finishes 
the cooling cycle on high speed. If the cooling equipment is energized to satisfy a 
dehumidify demand only (no cooling demand), the low cool lockout is not applied. 
•  ON - The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all cooling 
demands. 
NOTES 
•  If there is no valid outdoor temperature and the LOW COOL LOCKOUT is set to a 
temperature (not OFF or ON), the message OUTDOOR N/A is displayed in the banner 
and the low cool lockout setting is ignored (acts as if the setting is OFF).  
•  If the system does not have a 2-stage heat pump, this selection is not available.  
LOW HEAT LOCKOUT TEMPERATURE—Sets an outdoor air temperature below which low 
speed compressor heating is locked out. Below the specified air temperature, all heating 
demands that use the compressor use high speed compressor heating.   
Range 
•  OFF - Functionality disabled. Compressor heating always starts with first stage 
compressor Y1 and stages up to second stage Y1 and Y/Y2 when the demand is 
sufficient and staging and cycle timer constraints have been satisfied. 
•  20° – 50°F - Outdoor temperature below which both the first and second stages of 
the compressor are energized to satisfy all heating demands. This check is 
performed when the first stage of the compressor is energized. If at the time the 
compressor is energized, the outdoor air temperature is less than or equal to the 
LOW HEAT LOCKOUT TEMPERATURE, then the second stage of the compressor is 
energized also. When a cycle starts under a low heat lockout condition, it will finish 
the heating cycle on high speed.    
•  ON - The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all compressor 
heating demands, regardless of outdoor air temperature. 
NOTES 
•  If there is no valid outdoor temperature and the LOW HEAT LOCKOUT is set to a 
temperature (not OFF or ON), the message OUTDOOR N/A displays in the banner 
and the low heat lockout setting is ignored (acts as if the setting is OFF).  
•  If the system does not have a 2-stage heat pump, this selection is not available.