Using installer settings
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION ©2021
Installation Guide All rights reserved
38
HUMIDIFIER—Enables humidifier control functionality. When humidifier control is
enabled, the humidifier is energized if there is humidity demand and any heating
equipment is energized.
The output (Y3, O/B or W2) is a 24 Vac output only (sourced from R) and must be
isolated with a relay at the indoor equipment if 120 Vac is needed to interface to a
humidifier unit.
NOTE Humidifier functionality is not available if HEATING STAGES is set to NONE.
HUM OUTPUT—Select which output relay to use for the humidifier. The choices only
include outputs that are not already assigned to another function.
The output that is selected (Y3, O/B or W2) is used to control the humidifier equipment.
NOTE HUM OUTPUT is only available if the HUMIDIFIER setting is YES.
The HUM OUTPUT option is not available if the Y3, O/B and W2 relays are already being
used for other functions.
• The Y3 output is used for 3 stages of cooling, the humidifier, and the dehumidifier
setting of HumidiMiZer™.
• The O/B output is used for heat pump equipment, the humidifier, and the
dehumidifier setting of the HumidiMiZer™.
• The W2 output is used for 2 stages of heating, the humidifier, and the dehumidifier
setting of HumidiMiZer™.