EasyManuals Logo

Carrier SmartVu control User Manual

Carrier SmartVu control
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #145 background imageLoading...
Page #145 background image
SRDC-UG-2-14-000
REVISION
DATE
PAGE
19 Series Carrier®
SmartVu
TM
Controls IOM
2.3
Dec 4, 2020
145 OF 168
145
16
condfrze
NO_YES
NO
-
Condenser Frozen
17
rcysh_cm
NO_YES
NO
-
Recycle Shutdown Done
18
nrysh_cm
NO_YES
NO
-
NonRecycle Shutdown Done
19
alm_act
NO_YES
NO
-
In Alarm
20
over_act
NO_YES
NO
-
In Override
21
pg_act
NO_YES
NO
-
Purge Active
22
cm_stat1
-
0
-
Comp1 Run State Val
*Depends on the selected language (English by default).
SETPOINT - Setpoint
Name
Range
Default
Unit
Displayed text*
1
ecw_sp
-9.44 to 48.89
15 to 120
15.56
60
°C
°F
Cooling ECW Setpoint
2
lcw_sp
-12.22 to 48.89
10 to 120
7.22
45
°C
°F
Cooling LCW Setpoint
3
ecdw_sp
17.22 to 65.56
63 to 150
40.00
104
°C
°F
Heating ECDW Setpoint
4
lcdw_sp
20.00 to 65.56
68 to 150
45.00
113
°C
°F
Heating LCDW Setpoint
5
ice_sp
-9.44 to 15.56
15 to 60
4.44
40
°C
°F
Ice Build Setpoint
6
dem_base
10 to 100
100
%
Base Demand Limit
7
EWT_OPT
DSABLE_ENABLE
DSABLE
-
EWT Control Option

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier SmartVu control and is the answer not in the manual?

Carrier SmartVu control Specifications

General IconGeneral
BrandCarrier
ModelSmartVu control
CategoryControl Panel
LanguageEnglish

Related product manuals