95 
 
 
If the free cooling is activated the control shall take the following measure: 
If chiller is in not in OFF status, ignore the free cooling request (chiller will continue to run) until chiller 
shut down. 
Else 
Unit will be locked so the compressor cannot run 
             Condenser water pump output forced to ON 
             Evaporator water pump output forced to ON 
  Head Pressure valve is forced to the fully open position. 
    The 1st & 2nd IGV will be opened in the maximum open position  
The liquid bypass valve is forced to the fully open position 
The envelope stability control valve is forced to the fully open position  
The economizer isolation valve is forced to be fully open position 
  A Digital Output “free cooling active” will be energized 
             The free cooling valve is forced to the fully open position (19DV only)   
             A message (event 9) will be displayed on the chiller control display 
  Chiller status shall be “FREECOOL”   
5.35.  Marine Option 
Marine chillers are a little different from common chillers, and have a few new functions. 
5.35.1. Oil Stir Function 
If ”Option 2” -> ”Marine Option” is enabled, when chiller is not running, the oil pump will be switched on 
for 30 seconds every 3 hours, no matter oil heater is on or off. When oir stir is in progress, oil heater will 
be switched off. 
5.35.2. Power Request 
If  ”Option 2” -> ”
 
Marine Pwr Req Option” is enabled, when chiller is starting up, it will send power 
request signal and alert 104 while verifying water flow. After it receives the permission to start feedback, 
the start up will proceed. The power request signal will remain active till the compressor is switched on. If 
there is still no permission to start feedback 5 minutes after power request is sent, or permission to start 
feedback is deactivated before compressor is switched on, the start up process will terminate and trigger 
an alarm.